REMEHA Quinta Pro 30 Installation And Service Manual page 61

Wall-hung gas condensing boilers
Hide thumbs Also See for Quinta Pro 30:
Table of Contents

Advertisement

Quinta Pro 45 - 65 - 90 - 115
B
T002870-B
080310 - 123157-AA
7. Quinta Pro 115: If necessary, adjust the gas/air ratio using the
adjusting screw on the gas block (B).
O
/CO
control and setting values at part load for G25 (Gas L)
2
2
Boiler type
Setting value
Quinta Pro
O
(%)
2
30
3,9 ± 0.1
45
4,8 ± 0.1
65
4,8 ± 0.1
90
3.9 ± 0.1
115
3.9 ± 0.3
O
/CO
control and setting values at part load for G20 (Gas H)
2
2
Boiler type
Setting value
Quinta Pro
O
(%)
2
30
3,9 ± 0.1
45
4,8 ± 0.1
65
4,8 ± 0.1
90
3.9 ± 0.1
115
3.9 ± 0.3
O
/CO
control and setting values at part load for G31 (Propane)
2
2
Boiler type
Setting value
Quinta Pro
O
(%)
2
30
4,8 ± 0.1
45
4,8 ± 0.1
65
4,8 ± 0.1
90
4.8 ± 0.1
115
4.9 ± 0.2
Control value
CO
(%)
O
(%)
2
2
9.5 ± 0.1
3,9 ± 0.8
9.0 ± 0.1
4,8 ± 0.8
9.0 ± 0.1
4,8 ± 0.8
9,4 ± 0.2
3.9 ± 0.8
9.5 ± 0.2
3.9 ± 1.0
Control value
CO
(%)
O
(%)
2
2
9.5 ± 0.1
3,9 ± 0.8
9.0 ± 0.1
4,8 ± 0.8
9.0 ± 0.1
4,8 ± 0.8
9,5 ± 0.2
3.9 ± 0.8
9.5 ± 0.2
3.9 ± 1.0
Control value
CO
(%)
O
(%)
2
2
10.7 ± 0.1
4,8 ± 0.8
10.7 ± 0.1
4,8 ± 0.8
10.7 ± 0.1
4,8 ± 0.8
10,6 ± 0.2
4.8 ± 0.8
10,5 ± 0.1
4.9 ± 0.5
5. Start-up
CO
(%)
2
9.05 ± 0.4
9.0 ± 0.4
9.0 ± 0.4
9,4 ± 0.5
9.5 ± 0.5
CO
(%)
2
9.05 ± 0.4
9.0 ± 0.4
9.0 ± 0.4
9,5 ± 0.5
9.5 ± 0.5
CO
(%)
2
10.7 ± 0.5
10.7 ± 0.5
10.7 ± 0.5
10,6 ± 0.7
10,5 ± 0.5
59

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Quinta pro 90Quinta pro 115Quinta pro 45Quinta pro 65

Table of Contents

Save PDF