Switching Off The Appliance; Installation Shutdown; Antifreeze Protection - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Hide thumbs Also See for Quinta Pro 30:
Table of Contents

Advertisement

Quinta Pro 45 - 65 - 90 - 115
6

Switching off the appliance

6.1

Installation shutdown

6.2

Antifreeze protection

080310 - 123157-AA
If the central heating system is not used for a long period, we
recommend switching the boiler off.
4 Place the start/stop switch on Off.
4 Cut the gas supply.
4 Ensure that antifreeze protection is activated.
CAUTION
Drain the boiler and central heating system if you are not
going to use your home or the building for a long time and
there is a chance of frost.
4 Set the temperature control low, for example at 10°C.
To prevent radiators and the system from freezing in rooms where
there is a risk of frost (e.g. a garage or storage room), a frost
thermostat or outside sensor can be connected to the boiler.
¼ See paragraph: "Connect frost protection", page 36.
CAUTION
The anitfreeze protection does not function if the
4
boiler is switched off.
The integrated protection system only protects the
4
boiler, not the installation.
When the heating water temperature in the boiler falls by too much,
the integrated protection system in the boiler starts up. This protection
functions as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the heating pump continues to run for a short time.
6. Switching off the appliance
71