4.3.2.
5 0
4 Before mounting the boiler, decide on the ideal position for
0
mounting, bearing the Directives and the dimensions of the
appliance in mind.
4 When choosing the position for mounting the boiler, bear in mind
the authorised position of the combustion gas discharge outlets
m i
n .
and the air intake opening.
4 0
0
4 To ensure adequate accessibility to the appliance and facilitate
maintenance, leave enough space around the boiler.
7 5
0
3 5
0
m i
n .
2 5
0
0
5 0
T002599-B
4.3.3.
If the boiler is installed in a closed box, respect the minimum
dimensions given in the diagram opposite. Also allow openings to
obviate the following hazards:
4 Accumulation of gas
4 Heating of the box
Minimum cross section of the openings: S1 + S2 = 150 cm
Location of the appliance
WARNING
Fix the appliance to a solid wall capable of bearing
4
the weight of the appliance when full of water and fully
equipped.
It is forbidden to store inflammable products and
4
materials in the boiler room or close to the boiler,
even temporarily.
CAUTION
The boiler must be installed in a frost-free
4
environment.
An earthed electrical connection must be available
4
close to the boiler.
A connection to the mains drainage system for the
4
discharge of condensate must be available close to
the boiler.
Aeration
4. Installation
2
17