Technical information

Remeha Quinta 115

• High-efficiency
condensing boiler for wall
mounted installation
• Output: 18 - 115 kW

Advertisement

Table of Contents
loading

Summary of Contents for REMEHA Quinta 115

  • Page 1: Technical Information

    Technical information Remeha Quinta 115 • High-efficiency condensing boiler for wall mounted installation • Output: 18 - 115 kW...
  • Page 2: Table Of Contents

    Remeha Quinta 115 TABLE OF CONTENT PREFACE GENERAL DESCRIPTION OF THE BOILER CONSTRUCTION Boiler layout Operating principle TECHNICAL DATA AND DIMENSIONS Dimensions Technical data General Specification Options EFFICIENCY INFORMATION Annual efficiency Heat to water efficiency APPLICATION INFORMATION CONTROL AND SAFETY EQUIPMENT The control panel 6.1.1 General...
  • Page 3: Dhw Temperature Set Point

    7.4.3 Cold feed and expansion tank height for open vented systems 7.4.4 Safety valve 7.4.5 Gas connection 7.4.6 System pump 7.4.7 Waterflow Modular installations 7.5.1 Introduction 7.5.2 The Remeha Quinta cascade system 7.5.3 Independent installation DHW production ELECTRICAL INSTALLATION General Specifications 8.2.1 Electrical supply...
  • Page 4 Remeha Quinta 115 8.2.2 Control box 8.2.3 Fuse specification 8.2.4 Boiler temperature control 8.2.5 High limit temperature protection 8.2.6 Low-water protection (flow and content) External connections Boiler control 8.4.1 Modulating controls general (two wire control) 8.4.2 Analog control (0 -10 V dc) 8.4.3 On / off control (1 x no volt switched pair)
  • Page 5: Preface

    PREFACE These technical instructions contain useful and important information for the correct operation and maintenance of the Remeha HTG boiler, model Quinta 115. Read these instructions carefully before putting the boiler into operation, familiarise yourself with its control functions and operation, strictly observing the instructions given.
  • Page 6: General Description Of The Boiler

    Remeha Quinta 115 GENERAL DESCRIPTION OF THE BOILER The Remeha Quinta 115 is a wall hung condensing boiler which may be also installed free standing on a suitable frame (option). The one piece cast aluminium heat exchanger and other major components are contained within a sealed air box. This forms the main boiler casing with a removable front section for maintenance purposes.
  • Page 7: Construction

    CONSTRUCTION 2.1 Boiler layout Fig. 01 Boiler layout Remeha Quinta 115* 110397_09 110397_09 * the illustration can be slightly different Control panel Automatic air vent 10. Facility for incorporating a weather Air supply fan compensated boiler control (DIN- Gas combi-block (with governor)
  • Page 8: Operating Principle

    Remeha Quinta 115 2.2 Operating principle Combustion air is drawn into the closed air box by a variable speed fan, through the air inlet connection from the plant room (open flued) or from outside via the concentric flue system (room sealed). On the inlet side of the fan is a specially designed venturi which is connected to the outlet side of the gas combi block.
  • Page 9: Technical Data And Dimensions

    TECHNICAL DATA AND DIMENSIONS 3.1 Dimensions � � Fig. 02 Dimensions Remeha Quinta 115 05w4h7900024 + 00w4h7900048 Ê Return connection 1¼” BSP (m) É Flow connection 1¼” BSP (m) Ï Gas connection ¾” BSP (m) Ò Condensate connection 25 mm Ø o/d (plastic) Ñ...
  • Page 10: Technical Data

    Remeha Quinta 115 3.2 Technical data Boiler type Quinta 115 General Colour side and front casing BS RAL 9016 Colour instrument panel flap 7036 Boiler control options (External input) On/off, High/low, Analog 0 -10V (Two wire control) Communicating Modulation Nominal output (80/60ºC) 16,6 - 107 Nominal output (50/30ºC)
  • Page 11: General Specification

    V/Hz 230 / 50 Electric rating without pump 40 - 240 Insulation class Table 01 Technical data Remeha Quinta 115 * see par. 7.4.3 3.3 General Specification (to be read with above table) - One piece cast aluminium heat exchanger.
  • Page 12: Options

    , GCV = H APPLICATION INFORMATION The Quinta 115 can be used on all new and re-furbishment projects in both single and multiple configurations. Conventional and room sealed flue system capability means that the boiler can be sited almost anywhere within a building.
  • Page 13: Control And Safety Equipment

    For security the control has three levels of access: - User level - free access - Service level - access with service code by qualified personnel - Factory level - access by PC with factory code (Remeha only) 6.1.2 Layout of the control panel Fig. 03 Control panel 00.W4H.79.00044...
  • Page 14: Combined Key Functions (In Operating Mode Only)

    Remeha Quinta 115 a. ‘code’-display Indicates on user level: operating mode: only one digit 1 setting mode: digit with dot ! read-out mode: digit with flashing dot ! shut-off mode: letter b forced full load: letter h forced part load: letter l Additional indication on speed mode: alternate half digit <...
  • Page 15: Display Of Values With More Than Two Digits

    ‘s‘-key and r-symbol: - (symbol) not illuminated: HTG under normal control - red (symbol) on: HTG off (manual override) ‘e’-key and k-symbol: - (symbol) not illuminated: DHW under normal control - red (symbol) on: DHW off (manual override) [+]-key and q-symbol: - green (symbol) on: continuous pump operation - (symbol) not illuminated: pump under boiler control [-]-key and h-symbol:...
  • Page 16: Flow Diagram Control System

    Remeha Quinta 115 6.2 Flow diagram control system press the ‘m’ -key press the ‘s’-key ‘code’-display tdisplay Operating mode, only digit or letter see Par. 6.3 0 - 9,h,l,b Flow temperature or shut-off code Setting mode, digit or letter with user level, see Par.
  • Page 17 Forced part load time after start (HTG) Fan speed at start DHW control stop or boiler modulation set point (based on parameter #) DHW control mode HTG cut in dT (based on return) Boiler type intern Maximum delay time Start point for 0 V analog signal End point for 10 V analog signal Intern Read-out mode,...
  • Page 18: Operating Mode (X

    Remeha Quinta 115 service engineer level only: Speed mode, alternate half Fan speed see Par. 6.8 digit < Failure mode, flashing digit see Par. 6.9 Failure code Operating code during failure Flow temperature during failure Return temperature during failure DHW temperature during failure Table 03 Flow diagram control system 6.3 Operating mode (x[[)
  • Page 19: Shut-Off Mode (Bxx)

    Shut-off mode Forced full load. Forced part load. Table 04 Operating codes 6.4 Shut-off mode (bXX) During shut-off mode condition the code-display will show a b, whilst the t-display indicates the cause with two flashing dots. Table below details cause of shut-off mode. Code Description Maximum acceptable flow temperature rise exceeded.
  • Page 20: Setting Mode User Level (X

    Remeha Quinta 115 NOTE: Shut-off mode is a normal boiler operating function and does not represent a boiler failure. However, this may indicate a system problem, an internal boiler check or an incorrect parameter setting. 6.5 Setting mode user level (X[[)
  • Page 21: Flow Temperature Set Point (!)

    6.5.1 Flow temperature set point (!) The required flow temperature is adjustable from 20 to 90°C. Fig. 04 Typical setting change procedure 110397_5 6.5.2 Pump run on time HTG (@) Pump run on time can be adjusted (Please refer to installation contractor) - Press the ‘m’...
  • Page 22: Boiler Control Setting (A)

    Remeha Quinta 115 6.5.3 DHW temperature set point (3) The DHW temperature is adjustable from 20 to 75°C (factory default 55°C). Only with Broag DHW priority sensor. - Press the ‘m’ -key until the digit ! (with dot) appears in the ‘code’-display.
  • Page 23: Setting Mode Service Level (X00)

    Description t-display Operation mode Second segment [y HTG and DHW off HTG and DHW on HTG on and DHW off HTG off and DHW on Table 08 Boiler control option * NOTE: Booster function n/a in UK 6.6 Setting mode service level (X00) (only for the qualified service engineer with product knowledge) To prevent accidental, unauthorised access by non-qualified persons the control system requires an input code to gain access to the second level of boiler control.
  • Page 24 Remeha Quinta 115 Modulation start point dT 05 – 30 ºC (F/R) 00 internal (Chronotherm Interface selection (control control only) option) 01 external interface 10 – 05 read 1 - 5 °C DHW cut-in dT 06 read 10 °C 07 read 15 °C 08 read 20 °C...
  • Page 25: Flow Temperature Set Point During Forced Part Load ($)

    Start point for 0 V analog 5) (= -50) – 50 °C signal End point for 10 V analog 50 – (( (=299) °C signal (=100)* Intern Table 09 Settings service level *NOTE: see Par. 6.1.4 for values over two digits 6.6.1 Flow temperature set point during forced part load ($) Adjustable from 20 to 90°C.
  • Page 26: Interface Selection (()

    Remeha Quinta 115 6.6.6 Interface selection (() Adjustable 00 or 01. This value sets the control option. 01 for standard 0 -10 V external control. 00 for the Honeywell Chronotherm option. 6.6.7 DHW cut-in temperature (B) Adjustable from 01 to 20 °C (8 steps, see Table 09).
  • Page 27: Dhw Control Stop Set Point (I)

    Parameter H factory set must not be changed 6.6.10 DHW control stop set point (I) Adjustable from 00 - 30 °C. Refer to Par. 6.6.7. 6.6.11 DHW control option (J) This value sets the DHW control option. 00 Three way diverting valve (port A - HTG and Port B - DHW) 01 DHW pump 02 Inverted three way diverting valve (port B - HTG and Port A - DHW) Parameter L not applicable...
  • Page 28: Read-Out Mode (X00)

    Remeha Quinta 115 End point (10 V): adjustable between +51°C and (( (+299)°C . This value sets the required flow temp at 10 V signal input (restricted by the max flow set point). NOTE: These settings are only applicable when boiler control operation parameter (A) has the x value set to 4.
  • Page 29: Failure Mode (X00)

    Code Description Example 7000 r/m Fan speed 70 hundreds Fan speed 00 units > Table 11 Fan speed mode service level 6.9 Failure mode (x00) To check the latest failure with the accompanying operating codes and relevant temperatures. Using the ‘m’ -key, press repeatedly until 1 (flashing digit) appears in the ‘code’- display.
  • Page 30: Installation Instructions

    ACOPS and IEE regs.) Important: The Remeha Quinta 115 is a CE certified appliance and must not therefore be modified or installed in any way contrary to these “Installation and Maintenance Instructions”. These manufacturer’s Instructions must NOT be taken as overriding statutory obligations.
  • Page 31: Flue Gas Discharge And Air Supply

    7.3 Flue gas discharge and air supply 7.3.1 General The Remeha Quinta 115 is suitable for conventional room ventilated or room sealed operation. Specify at the time of ordering if the boiler is to be installed for twin pipe room sealed operation. In that case, the boiler will be supplied with an optional adaptor plate (concentric to twin pipe).
  • Page 32: Classification Due To Discharging Flue Gases

    Remeha Quinta 115 7.3.2 Classification due to discharging flue gases Classification according to CE: Type B23: Conventional room ventilated boiler without draft diverter. Air supply from boiler room: flue gas discharge on roof. Type B23P: Conventional room ventilated boiler without draft diverter. Air supply from boiler room: flue gas discharge on roof, metal flue gas discharge with CE symbol, meets pressure class P1.
  • Page 33: Material And Installation

    7.3.3 Material and installation Flue gas discharge: Rigid single walled: stainless steel (316), aluminium or plastic (to comply with building regulations). Flexible: stainless steel (316). Construction: all joints and seams should be gastight and watertight with the horizontal runs graded towards the boiler to allow condensate free drainage to the boiler. Horizontal lenghts in excess of 2M should incorporate a condensate drain.
  • Page 34: Single Boiler, Room Sealed Flue

    Eq. Length bend 90° Table 13 Calculation data conventional flue Example: Quinta 115, total length 15 m, 2 bends 45°. 15 m + 2 x 1.4 = 17.8 < 19: flue Ø 100mm OK. Note: If the design parameters are outside the values shown in the above table or there is any doubt over the flue system, please contact our technical department for calculation to be undertaken.
  • Page 35: Different Pressure Zones

    Eq. Length bend 90° Table 14 Calculation data room sealed applications Example: Quinta 115, total length 3 m, 1 bends 45°. 3 m + 1 x 2 = 5 m < 7 m: flue OK. Note: If the design parameters are outside the values shown in the above table or there is any doubt over the flue system, please contact our technical department for calculation to be undertaken.
  • Page 36: Hydraulic Installation

    Remeha Quinta 115 The Remeha Quinta boiler (twin connection only) is capable of operating with the air inlet and flue outlet in different pressure zones (CLV System). There are some restrictions to the flue/air inlet lengths and max height differences which have been detailed in Fig.
  • Page 37 As most systems contain a variety of metals, it is considered good practice to provide some form of water treatment in order to prevent or reduce the following: • Metallic corrosion • Formation of scale and sludge • Microbiological contamination •...
  • Page 38: Cold Feed And Expansion Tank Height For Open Vented Systems

    Health and Safety Executive publication (latest execution). The Remeha Quinta series boilers require a minimum static head of 5 m. For operation in open vented systems parameter ! (flow temperature setpoint) must be set to 75 and parameter * (boiler modulation start point) must be set to 15 7.4.4 Safety valve...
  • Page 39: The Remeha Quinta Cascade System

    7.5.2 The Remeha Quinta cascade system For installing 2 to 10 boilers, Remeha’s range of products includes systems that are very easy to install (quick assembly). The hydraulic and gas pipe work can be put together entirely without welding, using screw connections, compression connections and flanges.
  • Page 40 HTG demand. If no HTG demand, the selected pump will run on for a maximum of 5 minutes). A Broag high output indirect calorifier can be connected to the Remeha Quinta 115 in accordance with the schematic sketch shown (see Fig. 10).
  • Page 41 Flow and return header installation A flow and return header installation is shown in Fig. 11. The separated hydraulic groupes have system pumps, controlled by a cascade controller. The controller monitors the conditions from each group and varies the heat output to suit the demand.
  • Page 42: Electrical Installation

    Remeha Quinta 115 ELECTRICAL INSTALLATION 8.1 General The Remeha Quinta 115 is supplied as standard with electronic control and flame ionisation safety controls with a specially designed microprocessor at the heart of the control system. 8.2 Specifications 8.2.1 Electrical supply The Remeha Quinta 115 must have a permanent 230V-50Hz single phase supply rated at 6.3 A.
  • Page 43: Boiler Temperature Control

    ‘reset’-key on the control panel. 8.2.6 Low-water protection (flow and content) The Remeha Quinta 115 is supplied with a low-water protection on the basis of temperature measurement, see Fig. 22, Boiler sensor resistance/temp graph. By modulating back at the moment that the water flow threatens to fall too low, the boiler is kept operating for as long as possible.
  • Page 44: Boiler Control

    8. Interface for 0 -10 V control 5. 230 V power suppply 8.4 Boiler control The Remeha Quinta 115 can be controlled using one of the following methods: 8.4.1 Modulating controls general (two wire control) To make full use of the boiler’s modulating feature, an OpenTherm control can be ®...
  • Page 45: Analog Control (0 -10 V Dc)

    Change setting mode parameter ( to 00. Set the x value of the boiler control operation parameter (A) to 1. Modulating weather-compensated cascade controller Remeha has a controller set Celcia 20 / Celcia MC4 for this that can be supplied as accessory. - Celcia 20; Optimising / weather-compensated boiler control used in conjunction with the Celcia MC4 for multiple boilers.
  • Page 46 Remeha Quinta 115 On Input voltage On Input voltage [V On Input voltage [V On Input voltage Fig. 15 Ratio between voltage and temperature Input voltage Input voltage [V Input voltage Input voltage [V Fig. 16 Ratio between voltage and output...
  • Page 47: On / Off Control (1 X No Volt Switched Pair)

    8.5 DHW control (Broag priority) 8.5.1 Temperature control With a Remeha temperature sensor or with a standard (volt free) DHW thermostat connected to terminals 7 and 8. If the cable from the boiler sensor or -thermostat exceeds 3 meters, we advise you to use our EMC-filter (Broag supply).
  • Page 48: Remote Alarm And Boiler Run Indication

    Remeha Quinta 115 NOTE: A frost thermostat should preferably be installed in rooms with a high frost risk. Connect the frost thermostat in parallel to the room thermostat - connectors 3 and 4 of the terminal strip. Attention: • The integrated boiler protection described above will not provide complete system or fabric protection.
  • Page 49: Wiring Diagram

    ������� ������� ����� ������� ������� ����� ����������� ������� ����� ������������� ������� ������ �� �� �� �� �� �� �� �� �� �� � � � � � � � � � � � � � � � � �� � �...
  • Page 50: Commissioning

    Remeha Quinta 115 COMMISSIONING NOTE: Engineer to carryout pre-commissioning checks to ensure that the installation complies with current regulations Initial lighting The boiler is supplied as standard for use with Natural Gas and tested at an operating pressure of 20 mbar. The boiler must not be put into operation with a different type of gas without reference to Broag.
  • Page 51 15. Re-establish power supply to boiler and isolate controls. 16. Use manual override to start the boiler (press and hold for 5 seconds [-]-key (green LED should appear in h-symbol) 17. The boiler should start with the run sequence (3) indicated in the ‘code’-display, see Par.
  • Page 52 Remeha Quinta 115 Fig. 20 Flue gas measure point. 05.W4H.79.00004 full load part load Fan speed 7000 rpm 1300 rpm Checking value 4,7 ± 0,5* 4,3 ± 0,5 9,1 ± 0,3* 9,3 ± 0,3 Setting value 4,3 ± 0,2 9,3 ± 0,1...
  • Page 53: Shut-Down

    Complete commissioning sheet, recording boiler serial No and site details and return copy to Broag for record purposes NOTE: The Remeha Quinta 115 is supplied with a number of factory default settings which should be correct for most installations. If other setting values are required refer to Par.
  • Page 54: Fault-Finding

    Remeha Quinta 115 10 FAULT-FINDING 10.1 General (all installations) Check the following, in sequence (by service engineer): Step Signs Check points Actions Boiler display is blank. The mains voltage 230 Replace fuse if necessary, but check what circuit it was protecting and rectify The fuse in the euro- if faulty.
  • Page 55: Fault Codes

    With the Celcia Under the normal Communication MC4 or another operating condition, (connection) with the OpenTherm press the m key for 2 control unit is not in order controller: Check seconds: does the top or the control unit is the communication part not flash in the defective between controller...
  • Page 56 Remeha Quinta 115 Code Description Cause/check points and remedy Flame - Gas valve shuts but burner surface continues to glow simulation due to incorrect combustion. - Gas valve off but leaking on shut-down - burner flame continuing. Short circuit 24V Check wiring.
  • Page 57 Setting failure - check parameter D (second digit must be 0) Failure of - short circuit in flat cable: replace flat cable internal - water/condensation on display communication - possibly external EMC contamination Safety interlock - The safety interlock (on terminals 10 and 14 of the terminal strip) has tripped or the wire bridge has been removed.
  • Page 58: Inspection And Servicing Instructions

    (ie CORGI - ACOPS - etc.). 11.2 Annual Inspection The annual inspection (or after 1600 hours run) of the Remeha Quinta 115 as follows: - Check combustion characteristics, see Table 16. NOTE: When checking combustion the C0 levels should be in accordance with the Table 16 and Table 17.
  • Page 59 ��� ���� ��� ������ ����� ��� ����������� ����� ��� ��������� � ��� ��������� ����� ��� ������� ������ ��������� ����� �������� ������� �� �� �� ��� �� � ���������� ����� ������� ��� �� ��� �������� ����������� �������� ��� �� ��� �������� � ����������� �������� ��� �� ��� Fig.
  • Page 60: Maintenance

    Remeha Quinta 115 11.3 Maintenance If during the annual inspection combustion results indicate that the boiler is no longer operating at the optimum level, additional maintenance should be carried out as follows: NOTE: • Please ensure that the gas supply and mains power supply is isolated before any maintenance work is carried out on the boiler •...
  • Page 61: Cleaning The Burner Assembly

    Heat exchanger can be washed with clean water, if badly contaminated, special cleaning tool (supplied optional) can also be used. Care should be taken when using water in the confined space of the boiler casing to avoid contaminating the electrical controls.
  • Page 62 Remeha Quinta 115 11.11 Part list Quinta 115 boiler EVGBW4H085001b/07.04 Fig. 23 Quinta 115* * the illustration can be slightly different EVGBW4H0115001b...
  • Page 63 Insulation front plate heat exchanger Burner Furigas 115 kW Sealing ring flue Ø 100 Bolt M6 Sealing plate (black foam) Plate bottom casing Hinge pin Gasket (fan to venturi) Gasket front plate Quinta 45/115 Gasket for venturi Venturi CVI 050 Quinta 115 Screw M5x10...
  • Page 64 Remeha Quinta 115 Gasket gas combi-block/venturi O-ring gas pipe Ø 26.8 x 22 x 2.5 Return pipe Flange for gas combi-block Sealing plate (siphon black foam) Support bracket air inlet Washer spring ring a4,3 Gas combi-block VK8115VB1008B Box instrument panel Grommet Ø...
  • Page 66 Remeha Quinta 115...
  • Page 68 Broag Ltd. Remeha House Molly Millars Lane RG41 2QP WOKINGHAM, Berks. Tel: +44 118 9783434 © Copyright Fax: +44 118 9786977 All technical and technological information contained in these technical instructions, Internet: uk.remeha.com as well as any drawings and technical descriptions furnisched by us remain our property and may not be multiplied without our prior consent in writing.