5. Start-up
St
ºC
58
T001581-A
ºCºFh
barPsi
rpm
kWµA
l/min
± 30
T001998-A
B
T002868-B
5.4.3.
Setting the air/gas ratio (Part load)
1. Unscrew the plug of the flue gas measurement point.
2. Connect the combusted gas analyser.
WARNING
Ensure that the opening around the sensor is completely
plugged when taking measurements.
3. Set the boiler to part load. Press the [-] key several times until
l3 is displayed on the screen.
4. Measure the percentage of O
5. Compare the values measured with the set point values given in
the table (With closed air box):
6. Quinta Pro 30/45/65/90: If necessary, adjust the gas/air ratio
using the adjusting screw on the gas block(B).
Quinta Pro 45 - 65 - 90 - 115
or CO
in the flue gases.
2
2
080310 - 123157-AA