REMEHA Quinta Pro 30 Installation And Service Manual page 27

Wall-hung gas condensing boilers
Hide thumbs Also See for Quinta Pro 30:
Table of Contents

Advertisement

Quinta Pro 45 - 65 - 90 - 115
Type
Execution
B23
open
(1)
B23P
B33
open
C13
closed
C33
closed
closed/Cascade 4
(2)
C43
C53
closed
C63
closed
(3)
closed
C83
(4)
closed
C93
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
Type Execution
C93
Diameter
Rigid
100 mm
Flexible
100 mm
Concentric
60/100 mm
80/125 mm
100/150 mm
080310 - 123157-AA
Description
Without fire-stop approval.
4
Exhaust of combustion gases above the roof.
4
Air in the installation room.
4
Without fire-stop approval.
4
Common exhaust of combustion gases above the roof.
4
Common exhaust of combustion gases mixed in the air, air in the installation room (special
4
construction).
Vent in the outside wall.
4
The opening for the air-supply inlet is located in the same pressure zone as the vent (For example,
4
a common passage through the outside wall).
Exhaust of combustion gases above the roof.
4
The opening for the air-supply inlet is located in the same pressure zone as the vent (For example,
4
a concentric passage to the roof).
Common channelling for the air-supply and exhaust of combustion gases (CLV):
Concentric.
-
Eccentric ; Air supply from the shaft.
-
This also relates to the overpressure cascades.
4
Closed equipment.
4
Separate channelling for the air-supply.
4
Separate channelling for the combustion gases.
4
Terminating on different pressure surfaces.
4
The manufacturer delivers this type of equipment without a supply or exhaust system.
4
The equipment can be connected on a so-called semi-CLV system (with common combustion
4
gas exhaust).
Channel for the air-supply and exhaust fumes in a duct or surrounded by a sleeve:
4
Concentric.
-
Eccentric ; Air supply from the shaft.
-
Exhaust of combustion gases above the roof.
-
The opening for the air-supply inlet is located in the same pressure zone as the vent.
-
Minimum size of the duct or jacket.
∅ Channel
(Without air-supply)
60 mm
110 mm
80 mm
130 mm
160 mm
60 mm
110 mm
80 mm
130 mm
160 mm
120 mm
145 mm
170 mm
∅ Channel
⃞ Channel
(With air-supply)
(Without air-supply)
120 mm
110 x 110 mm
140 mm
130 x 130 mm
170 mm
160 x 160 mm
120 mm
110 x 110 mm
145 mm
130 x 130 mm
170 mm
160 x 160 mm
120 mm
120 x 120 mm
145 mm
145 x 145 mm
170 mm
170 x 170 mm
4. Installation
⃞ Channel
(With air-supply)
110 x 110 mm
130 x 130 mm
160 x 160 mm
110 x 110 mm
130 x 130 mm
160 x 160 mm
120 x 120 mm
145 x 145 mm
170 x 170 mm
25