Quinta Pro 45 - 65 - 90 - 115
L
080310 - 123157-AA
n Connection in areas of different pressure (C53, C83)
Combustion air supply and combustion gas discharge are possible in
various pressure zones, semi-CLV systems. With the exception of the
littoral zone. The maximum permissible difference in height between
the combustion air supply and the combustion gas discharge is 36
m.
Chimney length in the various pressure zones
Diameter
80 mm 20 m
90 mm 36 m
100 mm 36 m
T000780-C
110 mm 36 m
130 mm 36 m
n Reduction table
Pipe reductions per element used
Elbow 45°
Diameter
Pipe reduction Pipe reduction
80 mm
90 mm
100 mm
110 mm
130 mm
4.7.4.
Additional Directives
4 Connection of the combustion gas exhaust directly to the buildings
conduits is forbidden for condensation reasons.
4 If the supply conduits are to be used, they must have a hermetic
construction with thick walls and be made from rigid aluminium or
stainless steel. Flexible supply conduits made from plastic or
stainless steel are also permissible. Aluminium is permissible only
if there is no contact between the building supply section and the
combustion gas exhaust pipe.
4 Always clean the ducts thoroughly in cases where lining pipes are
used and/or a connection of the air-supply.
4 It must be possible to inspect the supply conduit.
4 For long, aluminium, combustion-gas exhaust pipes it is initially
necessary to consider the relatively high quantity of corrosive
products which are brought together with the condensate from the
exhaust pipe. The siphon on the equipment requires regular
cleaning or, preferably, an additional condensate collector can be
installed above the equipment.
Maximum length (L)
Quinta Pro
30
45
65
90
20 m
-
-
36 m
2 m
-
36 m
8 m
4 m
36 m
34 m
22 m
36 m
36 m
36 m
Elbow 90°
1,2 m
4,0 m
1,3 m
4,5 m
1,4 m
4,9 m
1,5 m
5,4 m
1,0 m
6,2 m
4. Installation
115
-
-
-
24 m
36 m
27