4. Installation
80/125 mm
100/150 mm
4.8
Electrical connections
28
4 If the regular formation of surplus condensates is to be expected
in the combusted gas discharge conduits (e.g. when the boiler is
running on high and, consequently, the combusted gases can only
be condensated in the boiler up to a point), we recommend
constructing the combusted gas discharge conduit in stainless
steel or synthetic materials. If you nonetheless opt for aluminium,
a high quality (approved brand) of very thick aluminium must be
chosen. The combusted gas discharge conduit must be
sufficiently inclined towards the boiler (at least 50 mm per metre)
and an adequate collection tank and condensates discharge
system constructed (at least 1 m before the boiler opening). The
condensates strainer must be inspected and, if necessary,
cleanable. The elbows fitted must be at more than 90° to
guarantee the provision of an adequate gradient and tightness on
the lip rings.
Please contact us for further information.
4.7.5.
Connection of the combustion gas exhaust
pipe
Insertion depth 3 cm
S
Mounting
Fit together the combustion gas exhaust pipes, without welding.
4
4
4
T001990-A
4.8.1.
Control unit
The boiler is not live- and neutral-sensitive. The boiler is fully pre-
wired. All external connections can be made on the connection
connector (low voltage). The main characteristics of the control unit
are described in the table below.
Power supply voltage
Rating of the main fuse F1 (230 VAC) 6.3 AT
Fuse rating F2 (230 VAC)
Fan
The pipes must allow no leakage of flue gases and be
resistant to corrosion.
Connect the pipes together without stress between
the sections.
The horizontal sections will be constructed with a
gradient of 50 mm per metre: Boiler orientation.
230 VAC/50Hz
2 AT
230 VAC
Quinta Pro 45 - 65 - 90 - 115