CPU Unit Operation Status Indicators
You can check the CPU Unit status with the indicators at the top of the front panel of the CPU Unit.
The following table describes these indicators.
Indicator
RUN
Green
ERROR
Red
BUSY
Yellow
NJ-series CPU Unit Hardware User's Manual (W500)
Color
Status
Lit
The CPU Unit is in normal operation in RUN mode. (The user
program is in execution.)
Flashing (3-s
An Incorrect Power Supply Unit Connected error occurred. (A CJ-
intervals)
series Power Supply Unit is connected in the CPU Rack.) The
CPU Unit will not operate and the ERROR indicator will light.
Flashing (1-s
The CPU Unit is starting (entering RUN mode or PROGRAM
intervals)
mode at startup).
Not lit
Operation is stopped in PROGRAM mode, when a CPU Unit
reset is in progress, or when any of the following errors occurs.
• Controller error in the major fault level
• CPU error (WDT error)
Lit
Self-diagnosis found one of the following errors.
• Controller error in the major fault level
• CPU error (WDT error)
The CPU Unit operation will stop, and all outputs will turn OFF.
Flashing (1-s
Self-diagnosis found one of the following errors.
intervals)
• Controller error in the partial fault level (an error in which all
• Controller error in the minor fault level (an error in which partial
CPU Unit operation will continue for either of these errors.
Operation will stop for the Function Module in which a Controller
error in the partial fault level occurred.
Operation will continue for the Function Module in which a Con-
troller error in the minor fault level occurred.
Not lit
The CPU Unit is in normal operation, a CPU reset is in progress,
or monitored information occurred. (CPU Unit operation will con-
tinue.)
Flashing
Built-in non-volatile memory access in progress.
Not lit
Other than the above.
Meaning
control of a Function Module is disabled)
control of a Function Module is disabled)
3 Configuration Units