Event name
Non-volatile Memory Data Corrupted
Meaning
A file that must be in non-volatile memory is missing or corrupted.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The Controller power supply was
turned OFF while the BUSY indicator
was lit.
The power supply to the Controller
was interrupted momentarily while the
BUSY indicator was lit.
The CPU Unit has failed.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
NJ-series CPU Unit Hardware User's Manual (W500)
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Clear all of memory and then down-
load the project from the Sysmac Stu-
dio.
If this error remains even after making
the above corrections, replace the
CPU Unit.
5 Troubleshooting
Event code
10020000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Stops.*
Name
---
Prevention
Do not turn OFF the power supply
while the BUSY indicator is lit.
Take appropriate measures to ensure
that the specified power with the rated
voltage and frequency is supplied in
places where the power supply is
unstable.
None
At power ON or
Controller reset
System
5
5-33