Omron NJ501-1400 User Manual page 194

Nj-series cpu unit hardware
Hide thumbs Also See for NJ501-1400:
Table of Contents

Advertisement

5 Troubleshooting
Event code
Event name
10080000 hex
Main Memory
Check Error
100A0000 hex
Data Not
(Ver. 1.10 or
Saved to Bat-
later)
tery-backup
Memory
100B0000 hex
Non-volatile
Memory Data
Corrupted
100C 0000 hex
Event Level
(Ver. 1.03 or
Setting Error
later)
40010000 hex
PLC System
Processing
Error
40020000 hex
PLC System
Processing
Error
40030000 hex
PLC System
Processing
Error
00070000 hex
Real-Time
Clock
Stopped
00080000 hex
Real-Time
Clock Failed
000B0000 hex
Low Battery
Voltage
000C 0000 hex
CPU Unit
Overheat
5-14
Meaning
Assumed cause
An error was
• Conductive material has gotten
detected in the
inside.
memory check of
• Noise
the main memory in
• There is a software error.
the CPU Unit.
• The CPU Unit has failed.
An error occurred in
• An error occurred in the soft-
the software and
ware.
data could not be
saved in battery-
backup memory
during power-OFF
processing.
A file that must be
• The Controller power supply
in non-volatile
was turned OFF while the
memory is missing
BUSY indicator was lit.
or corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the BUSY indicator
was lit.
• The CPU Unit has failed.
The settings in the
• The event level settings are not
event level setting
correct because the power sup-
file are not correct.
ply to the Controller was inter-
rupted or communications with
the Sysmac Studio were dis-
connected during a download
of the event level settings.
• The event level settings are not
correct because the power sup-
ply to the Controller was inter-
rupted during a Clear All
Memory operation.
• Non-volatile memory failed.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
The oscillation of
• The battery voltage is low.
the real-time clock
• The battery connector has
stopped. The real-
come loose.
time clock is set to
• The Battery is missing.
an illegal time.
The real-time clock
• The CPU Unit clock has failed.
in the CPU Unit
failed.
The voltage of the
• The battery voltage is low.
Battery has
• The battery connector has
dropped.
come loose.
• The Battery is missing.
The temperature
• The ambient operating tem-
inside the CPU Unit
perature is too high.
exceeded the spec-
ified value.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
U
S
S
U
S
NJ-series CPU Unit Hardware User's Manual (W500)
Reference
page 5-34
page 5-35
page 5-36
page 5-37
page 5-37
page 5-38
page 5-38
page 5-39
page 5-39
page 5-40
page 5-40

Hide quick links: