5 Troubleshooting
Event name
SD Memory Card Data Corrupted
Meaning
A file that must be in the SD Memory Card is missing or corrupted.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
_Card1Ready
Cause and
Assumed cause
correction
The Controller power supply was
turned OFF while the SD BUSY indi-
cator was lit.
The power supply to the Controller
was interrupted momentarily while the
SD BUSY indicator was lit.
The SD Memory Card was removed
while the SD PWR indicator was lit.
The SD Memory Card is damaged.
Attached
None
information
Precautions/
The error is detected at power ON or at a Controller reset only when SD Memory Card diagnosis at startup is enabled.
Remarks
You can change the event level to the minor fault level. If you change the level to the minor fault level, the Recovery
column above will be changed to "Error reset."
5-44
Source details
Observation
Recovery
Continues.
Operation
Data type
BOOL
Correction
Format the SD Memory Card and
download the correct file.
If the error cannot be cleared with the
above corrections, replace the SD
Memory Card with one that operates
normally.
Event code
10060000 hex
None
Detection
timing
---
Log category
SD PWR indicator is not lit. You can format the SD Mem-
ory Card from the Sysmac Studio. Normal user program
operation may not be possible.
Name
SD Memory Card Ready Flag
Prevention
Do not turn OFF the power supply
while the SD BUSY indicator is lit.
Take appropriate measures to ensure
that the specified power with the rated
voltage and frequency is supplied in
places where the power supply is
unstable.
Do not remove the SD Memory Card
while the SD PWR indicator is lit.
None
NJ-series CPU Unit Hardware User's Manual (W500)
At power ON or
Controller reset
System

Hide quick links: