Cause and
Assumed cause
correction
The model of the CPU Unit to which
to transfer the files is not the same as
the model of the CPU Unit of the
backup files on the SD Memory Card.
The CPU Unit is write-protected.
Required files are not set to transfer
in the setting of the _Card1PrgTrans-
ferCmd system-defined variable.
Reading the data for the SD Memory
Card program transfer failed because
the SD Memory Card is faulty or not
formatted correctly.
The SD Memory Card is damaged.
The database connection service ver-
sion of the CPU Unit to which to
transfer the files is older than the
database connection service version
of the backup files on the SD Memory
Card.
The robot version of the CPU Unit to
which to transfer the files is older than
the robot version of the backup files
on the SD Memory Card.
NJ-series CPU Unit Hardware User's Manual (W500)
Correction
Replace the CPU Unit with a CPU
Unit that has the same model as the
CPU Unit that was used to create the
backup files.
Or, place the backup files with the
correct model for the used CPU Unit,
in the folder specified by the
_Card1PrgTransferCmd.DirName
system-defined variable.
If you transfer SD Memory Card pro-
grams, select the Do not use Option
for the Write protection at startup set-
ting of the CPU Unit.
Make sure that TRUE is set in the
_Card1PrgTransferCmd system-
defined variable to transfer required
files.
Perform the same corrective mea-
sures as for when the format of the
SD Memory Card is not correct or the
SD Memory Card is damaged.
If none of the above causes applies,
replace the SD Memory Card.
Replace the CPU Unit with a CPU
Unit that has the same or a newer
database connection service version
than the database connection service
version of the CPU Unit that was used
to create the backup files. Or, place
the backup files with the correct data-
base connection service version for
the CPU Unit, in the folder specified
by the _Card1PrgTransferCmd.Dir-
Name system-defined variable.
Replace the CPU Unit with a CPU
Unit that has the same or a newer
robot version than the robot version of
the CPU Unit that was used to create
the backup files. Or, place the backup
files with the correct robot version for
the CPU Unit, in the folder specified
by the _Card1PrgTransferCmd.Dir-
Name system-defined variable.
5 Troubleshooting
Prevention
Make sure that the model of the CPU
Unit is the same as the model of the
CPU Unit that was used to create the
backup files.
If you transfer SD Memory Card pro-
grams, select the Do not use Option
for the Write protection at startup set-
ting of the CPU Unit.
Make sure that TRUE is set in the
_Card1PrgTransferCmd system-
defined variable to transfer required
files.
Perform the same preventive mea-
sures as for the following events: SD
Memory Card Invalid Format or Faulty
SD Memory Card.
Do not remove the SD Memory Card
or turn OFF the power supply while
the SD BUSY indicator is lit. Or,
replace the SD Memory Card periodi-
cally according to the write life of the
SD Memory Card.
Make sure that the database connec-
tion service version of the CPU Unit
and the database connection service
version of the backup files are com-
patible.
Make sure that the robot version of
the CPU Unit and the robot version of
the backup files are compatible.