5 Troubleshooting
Event code
Event name
10340000 hex
Error in Exe-
(Ver. 1.11 or
cuting SD
later)
Memory Card
Program
Transfer
4011 0000 hex
PLC Function
Processing
Error
40160000 hex
Safe Mode
(Ver. 1.02 or
earlier)
44420000 hex
PLC Function
(Ver. 1.05 or
Processing
later)
Error
40120000 hex
PLC Function
Processing
Error
40130000 hex
PLC Function
Processing
Error
10230000 hex
Event Log
Save Error
10260000 hex
Trace Set-
ting Transfer
Failure
5-22
Meaning
Assumed cause
The SD Memory
• It was not possible to read the
Card program
data for SD Memory Card pro-
transfer ended in an
gram transfers.
error.
• The SD Memory Card was
removed during a SD Memory
Card program transfer.
• There are no backup files in
such a folder on the SD Mem-
ory Card as specified by the
_Card1PrgTransferCmd.Dir-
Name system-defined variable.
• The backup files in such a
folder on the SD Memory Card
as specified by the _Card1Prg-
TransferCmd.DirName system-
defined variable are corrupted.
• The SD Memory Card is dam-
aged.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
The Controller
• The power supply was turned
started in Safe
ON to the Controller when Safe
Mode.
Mode was set on the DIP
switch on the CPU Unit.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in part of
ware.
the PLC Function
Module.
Saving the event
• A low battery voltage prevented
log failed.
retention of memory during a
power interruption. (NJ/NX-
series)
• A forced shutdown was per-
formed. (NY-series)
• Data in the event log area are
invalid. (NY-series)
• Data in the NX Unit event log
area are invalid. (NX1P2 CPU
Unit)
The power supply
• The power supply was inter-
was interrupted
rupted while transferring the
while transferring
trace settings.
the trace settings.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
NJ-series CPU Unit Hardware User's Manual (W500)
Reference
page 5-65
page 5-66
page 5-66
page 5-67
page 5-67
page 5-68
page 5-68
page 5-69