Advertisement

Event name
Event Level Setting Error
Meaning
The settings in the event level setting file are not correct.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The event level settings are not cor-
rect because the power supply to the
Controller was interrupted or commu-
nications with the Sysmac Studio
were disconnected during a download
of the event level settings.
The event level settings are not cor-
rect because the power supply to the
Controller was interrupted during a
Clear All Memory operation.
Non-volatile memory failed.
Attached
None
information
Precautions/
None
Remarks
*1 This event code occurs for unit version 1.03 or later of the CPU Unit.
*2 For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
Event name
PLC System Processing Error
Meaning
A fatal error was detected in the PLC Function Module.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An error occurred in the software.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
NJ-series CPU Unit Hardware User's Manual (W500)
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Perform a Memory All Clear operation
and then transfer the event level set-
ting file again.
If the error persists even after you
make the above correction, replace
the CPU Unit.
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Contact your OMRON representative.
5 Troubleshooting
Event code
100C0000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
*2
Stops.
Name
---
Prevention
Do not interrupt the power supply to
the Controller or disconnect commu-
nications with the Sysmac Studio
during a download of the event level
settings.
Do not interrupt the power supply to
the Controller during a Clear All Mem-
ory operation.
None
Event code
40010000 hex
None
Detection
timing
Cycle the power
Log category
supply.
*
Stops.
A connection to the Sysmac Studio is not possible.
Name
---
Prevention
None
*1
At power ON or
Controller reset
System
5
Continuously
System
5-37