Omron NJ501-1400 User Manual page 203

Nj-series cpu unit hardware
Hide thumbs Also See for NJ501-1400:
Table of Contents

Advertisement

Event code
Event name
10290000 hex
Backup
(Ver. 1.03 or
Failed to
later)
Start
102A0000 hex
Backup
(Ver. 1.03 or
Failed
later)
NJ-series CPU Unit Hardware User's Manual (W500)
Meaning
Assumed cause
An error was
• An SD Memory Card is not
detected in pre-
inserted.
execution checks
• The SD Memory Card type is
for a backup opera-
not correct.
tion.
• The format of the SD Memory
Card is not correct.
• The SD Memory Card is write
protected.
• The Prohibiting backing up data
to the SD Memory Card param-
eter is set to prohibit backing up
data to an SD Memory Card.
• Another backup operation is in
progress.
• Synchronization, online edit-
ing, or the Clear All Memory
operation is in progress.
• The backup was canceled by
the user.
• The online connection with the
Sysmac Studio was discon-
nected.
• The SD Memory Card is dam-
aged.
The backup opera-
• The capacity of the SD Memory
tion ended in an
Card is insufficient.
error.
• It was not possible to save the
data that was specified for
backup.
• The SD Memory Card was
removed during a backup oper-
ation.
• Failed to back up Unit or slave.
• The backup was canceled by
the user.
• Execution of the Save Cam
Table instruction or changing
the CPU Unit name is in prog-
ress.
• The online connection with the
Sysmac Studio was discon-
nected.
• It was not possible to save the
data that was specified for
backup to the computer.
• The SD Memory Card is dam-
aged.
5 Troubleshooting
Level
Maj
Prt
Min
Obs Info
S
page 5-69
S
page 5-71
Reference
5
5-23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents