Omron NJ501-1400 User Manual page 238

Nj-series cpu unit hardware
Hide thumbs Also See for NJ501-1400:
Table of Contents

Advertisement

5 Troubleshooting
Event name
Illegal User Program/Controller Configurations and Setup
Meaning
The upper limit of the usable memory was exceeded or the user program or Controller Configurations and Setup is cor-
rupted.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The upper limit of the data size was
exceeded.
The main memory capacity was
exceeded.
Non-volatile memory is deteriorating
or has failed.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
5-58
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
If an event on restrictions on the num-
ber of items used occurred at the
same time as this event, correct the
user program and settings so that the
number of items used is not
exceeded and then download the
data again.
If an event on restrictions on the num-
ber of items used did not occur at the
same time as this event, perform the
Clear All Memory operation, cycle the
power supply, and then confirm that
this event was cleared. If it was
cleared, reduce the size of the proj-
ect, e.g., by sharing programming,
and then download the project again.
If this error persists even after you
implement the above two corrections,
replace the CPU Unit.
Event code
10250000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Stops.*
Name
---
Prevention
None
NJ-series CPU Unit Hardware User's Manual (W500)
At download,
power ON, or
Controller reset
System

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents