Omron NJ501-1400 User Manual page 318

Nj-series cpu unit hardware
Hide thumbs Also See for NJ501-1400:
Table of Contents

Advertisement

Appendices
 CJ1W-OD202 Transistor Output Unit (8 Points)
Name
Model
Rated Voltage
Operating Load Voltage Range
Maximum Load Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Load Short-circuit Protection
Line Disconnection Detection
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
Circuit Configuration
A-34
8-point Transistor Output Unit with Terminal Block (Sourcing Outputs)
CJ1W-OD202
24 VDC
20.4 to 26.4 VDC
2 A/point, 8 A/Unit
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
Detection current: 6 A min.
Automatic restart after error clearance. (Refer to page A-95.)
Detection current: 200 mA (Refer to page A-95.)
20 M between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current
of 10 mA max.
8 (4 points/common, 2 circuits)
110 mA max.
None
24 VDC, 50 mA min.
120 g max.
Output indicator
ERR indicator
• When an overcurrent or line disconnection is detected, the ERR indicator will light. At the same
time, the corresponding bit (two points per bit) in the Basic I/O Unit Information Area system-
defined variable will change to TRUE.
Signal name
COM0 (+V)
Jxx_Ch1_Out00
to
Jxx_Ch1_Out03
0 V
COM1 (+V)
Jxx_Ch1_Out04
to
Jxx_Ch1_Out07
0 V
NJ-series CPU Unit Hardware User's Manual (W500)