4 Installation and Wiring
DIN Track and Accessories
Use the DIN Track and DIN Track End Plates shown below. Secure each DIN Track inside a control
panel with at least three screws.
• DIN Track
Model numbers: PFP-50N (50 cm), PFP-100N (100 cm), PFP-100N2 (100 cm)
Secure the DIN Track to the control panel using M4 screws separated by 210 mm (6 holes) or less and
using at least 3 screws. The tightening torque is 1.2 N·m.
PFP-100N2 DIN Track
4.5
25
15
10
PFP-100N/50N DIN Track
4.5
15
25
10
• PFP-M DIN Track End Plates (2 required)
4-18
Twenty-eight, 25 × 4.5 oblong holes
25
15
25
25
10
1000
25
25
25
15 (5)*
10
1000 (500)*
16
30 0.3
27
24
29.2
1
1.5
7.3 0.15
35 0.3
27 0.15
1
* PFP-50N dimensions are
given in parentheses.
NJ-series CPU Unit Hardware User's Manual (W500)