4 Installation and Wiring
Grounding
• To help prevent electrical shock, ground the ground terminal (GR:
less than 100  using a 14-gauge wire (minimum cross-sectional area of 2 mm
• The line ground terminal (LG:
errors or electrical shocks are a problem, connect the line ground terminal to the ground terminal and
ground both with a ground resistance of less than 100 .
• If the LG and GR terminals are connected, ground to a resistance of 100  or less to prevent electric
shock.
• The ground wire should not be more than 20 m long.
• The NJ-/CJ-series Controllers are designed to be mounted so that they are isolated (separated) from
the mounting surface to protect them from the effects of noise in the installation environment (e.g.,
the control panel).
• Do not share the Controller's ground with other equipment or ground the Controller to the metal struc-
ture of a building. Doing so may worsen operation. Whenever possible, use an independent ground
(with the ground pole separated by a minimum of 10 m from any other ground pole).
• Ground to 100  or less, and if possible use a separate ground from those of other devices. (Refer to
figure (a) in the diagram below.)
• If using an independent ground is not possible, then use a common ground as shown in figure (b).
Connect to the ground pole of the other device.
 Crimp Terminals
The terminals on the Power Supply Unit are M4, self-raising terminals with screws.
Precautions for Safe Use
• Use crimp terminals for wiring.
• Do not connect bare stranded wires directly to terminals.
• Tighten the terminal block screws to the torque of 1.2 N·m.
• Use crimp terminals (M4) having the dimensions shown below.
4-30
LG (Noise-filter neutral terminal)
Ground this terminal to less than 100 Ω
to improve noise resistance and prevent
electric shock.
GR (Ground terminal)
Ground this terminal to less than 100 Ω
to prevent electric shock.
) is a noise-filtered neutral terminal. If noise is a significant source of
Controller
Controller
Other
device
Ground of
100 Ω or less
(a) Independent grounds:
(b) Common ground:
Best
Grounding Methods
Controller
Other
device
(c) Common ground:
Acceptable
Incorrect
NJ-series CPU Unit Hardware User's Manual (W500)
) with a ground resistance of
2
).
Other
device