2
SPECIFICATIONS
This section describes the specifications of the master/intelligent device module.
2.1

General Specifications

General specifications other than the following are the same as the CPU module to be connected.
Refer to the following manual for general specifications.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
Item
Withstand voltage
Insulation resistance
2.2

Power Supply Specifications

Shows power supply specifications.
Item
External power supply
2.3

Performance Specifications

Shows performance specifications.
Item
CC-Link compatible version
Station type
Station No.
Connectable station type (when
operating as a master station)
Transmission speed
Maximum number of connected stations
(when operating as a master station)
Number of occupied stations (when
operating as an intelligent device station)
Maximum number
CC-Link Ver.1
of link points per
system (when
operating as a
master station)
CC-Link Ver.2
Link points per remote station/intelligent
device station
Communication method
Synchronization method
Encoding method
Network topology
2 SPECIFICATIONS
18
2.1 General Specifications
Specifications
500 V AC for 1 minute
10 M or more with 500 V DC
insulation resistance meter
Specifications
Power-supply voltage
24 V DC + 20%, -15%
Allowable momentary
Continues operation against momentary power failure of 1 ms or less
power failure time
Current consumption
100 mA
Description
Ver.2.00 (Ver.1.10 is also supported)
Master station or intelligent device station
• Master station: 0
• Intelligent device station: 1 to 64
Remote I/O station, remote device station, intelligent device station (local station and standby master station
*1
cannot be connected)
• Master station: Selected from 156 kbps/625 kbps/2.5 Mbps/5 Mbps/10 Mbps
• Intelligent device station: Selected from 156 kbps/625 kbps/2.5 Mbps/5 Mbps/10 Mbps/Auto-tracking
• Remote I/O station: Up to 12 stations (a total point of inputs/outputs of remote I/O stations is 384 points or less)
• Total of intelligent device stations + remote device stations: Up to 12 stations (a total point of inputs/outputs of
intelligent device stations + remote device stations is 384 points or less)
1 station to 4 stations (changed according to the setting of engineering tools)
• Remote input/output (RX, RY): 768 points (remote I/O station: 384 points
device station: 384 points a total of 768 points)
• Remote register (RWw): 48 points (master station  remote device station/intelligent device station)
• Remote register (RWr): 48 points (remote device station/intelligent device station  master station)
• Remote input/output (RX, RY): 768 points (remote I/O station: 384 points
device station: 384 points a total of 768 points)
• Remote register (RWw): 96 points (master station  remote device station/intelligent device station)
• Remote register (RWr): 96 points (remote device station/intelligent device station  master station)
Page 19 Number of link points for each number of occupied stations
Broadcast polling method
Frame synchronization method
NRZI method
Bus (RS-485)
Between all terminals and the ground terminal
*2
, remote device station + intelligent
*2
, remote device station + intelligent