2
SPECIFICATIONS
This section describes the specifications of the master/intelligent device module.
2.1
General Specifications
General specifications other than the following are the same as the CPU module to be connected.
Refer to the following manual for general specifications.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
Item
Withstand voltage
Insulation resistance
2.2
Power Supply Specifications
Shows power supply specifications.
Item
External power supply
2.3
Performance Specifications
Shows performance specifications.
Item
CC-Link compatible version
Station type
Station No.
Connectable station type (when
operating as a master station)
Transmission speed
Maximum number of connected stations
(when operating as a master station)
Number of occupied stations (when
operating as an intelligent device station)
Maximum number
CC-Link Ver.1
of link points per
system (when
operating as a
master station)
CC-Link Ver.2
Link points per remote station/intelligent
device station
Communication method
Synchronization method
Encoding method
Network topology
2 SPECIFICATIONS
18
2.1 General Specifications
Specifications
500 V AC for 1 minute
10 M or more with 500 V DC
insulation resistance meter
Specifications
Power-supply voltage
24 V DC + 20%, -15%
Allowable momentary
Continues operation against momentary power failure of 1 ms or less
power failure time
Current consumption
100 mA
Description
Ver.2.00 (Ver.1.10 is also supported)
Master station or intelligent device station
• Master station: 0
• Intelligent device station: 1 to 64
Remote I/O station, remote device station, intelligent device station (local station and standby master station
*1
cannot be connected)
• Master station: Selected from 156 kbps/625 kbps/2.5 Mbps/5 Mbps/10 Mbps
• Intelligent device station: Selected from 156 kbps/625 kbps/2.5 Mbps/5 Mbps/10 Mbps/Auto-tracking
• Remote I/O station: Up to 12 stations (a total point of inputs/outputs of remote I/O stations is 384 points or less)
• Total of intelligent device stations + remote device stations: Up to 12 stations (a total point of inputs/outputs of
intelligent device stations + remote device stations is 384 points or less)
1 station to 4 stations (changed according to the setting of engineering tools)
• Remote input/output (RX, RY): 768 points (remote I/O station: 384 points
device station: 384 points a total of 768 points)
• Remote register (RWw): 48 points (master station remote device station/intelligent device station)
• Remote register (RWr): 48 points (remote device station/intelligent device station master station)
• Remote input/output (RX, RY): 768 points (remote I/O station: 384 points
device station: 384 points a total of 768 points)
• Remote register (RWw): 96 points (master station remote device station/intelligent device station)
• Remote register (RWr): 96 points (remote device station/intelligent device station master station)
Page 19 Number of link points for each number of occupied stations
Broadcast polling method
Frame synchronization method
NRZI method
Bus (RS-485)
Between all terminals and the ground terminal
*2
, remote device station + intelligent
*2
, remote device station + intelligent