11.
In "Remote Device Initial Setting Procedure Registration" window, right-click the icon and click "Hexadecimal" of the
"Input Format." Set the items in the initial settings as follows.
• Initial setting of AJ65VBTCU-68DAVN (station No.1)
Setting the initial setting executes the following processing from the first condition.
Condition
Description
1st
The CH.1 and CH.2 are set to the analog output enable.
2nd
An output range is set.
• CH.1: 0 to 5 V
• CH.2: User range setting 1 (-10 to +10 V)
3rd
HOLD/CLEAR is set.
• CH.1: CLEAR
• CH.2: CLEAR
4th
Initial data processing completion flag is turned on.
5th
Initial data setting request flag is turned on.
6th
Initial data processing completion flag is turned off.
7th
Initial data setting request flag is turned off.
12.
Write the set parameters to the CPU module on the master station. Then reset the CPU module or power off and on the
system.
[Online]  [Write to PLC]
For the parameters, refer to the following.
Page 58 PARAMETER SETTINGS
8.2 Example of Communications Between a Master Station, a Remote Device Station and a Remote I/O Station
8 PROGRAMMING
81
8