Setting method
■Setting of the Input Data from Data Link Faulty Station
Select the input data setting under "Supplementary Cyclic Settings" in "Application Settings." (Page 71 Supplementary
cyclic settings)
■Data Link Setting at CPU Failure
Select the data link setting under "Supplementary Cyclic Settings" in "Application Settings." (Page 71 Supplementary
cyclic settings)
Status difference between a master station and a slave station at an error
The station status at an error varies depending on the combination of "Input Data from Data Link Faulty Station", "Output
Mode upon CPU STOP", "Data Link Setting at CPU Failure," and "Output Mode Setting at CPU Error" under "Supplementary
Cyclic Settings" in "Application Settings." When configuring the settings, consider the station status at errors listed below.
■Status of a master station (when operating as a master station) and remote I/O station
Data link status
When the CPU
"Output Mode
module of the
Setting upon
master station is set
CPU Error"
to STOP at an error
(setting in the
("Data Link Setting
master station)
at CPU Failure" =
"Continue the Data
Link")
When the CPU
"Output Data
module of the
Setting during
master station is set
CPU STOP"
to STOP
(setting in the
master station)
When data link for
"Input Data
the entire system is
Setting from
stopped
Data Link
Faulty Station"
(setting in the
master station)
When a
"Input Data
communication
Setting from
failure (such as
Data Link
power off) occurs in
Faulty Station"
a remote I/O station
(setting in the
master station)
When a
"Input Data
communication
Setting from
failure (such as
Data Link
power off) occurs in
Faulty Station"
a remote device
(setting in the
station
master station)
When a
"Input Data
communication
Setting from
failure (such as
Data Link
power off) occurs in
Faulty Station"
an intelligent device
(setting in the
station
master station)
*1 The target data is cleared to transmit 0 data to the slave station, but the value of the target data storage destination buffer memory in the
master station is retained. When an non-latch device (including Y devices) is set as a refresh device, also clears the target data storage
buffer memory in the master station.
*2 Clears when a non-latch device (including Y devices) is set as a refresh device. When setting the latch device or without link refresh
setting, holds or clears according to "Output Data Setting at CPU STOP."
Master station (when operating as a master station)
Remote input (RX)
Clear
Continue
Hold
Sends 0
Continue
data
Sends
output
data
*4
Clear
Clear
Hold
Hold
Clear
Clears the receive area
from the communication
failure station
Hold
Holds the receive area
from the communication
failure station
Clear
Clears the receive area
from the communication
failure station
Hold
Holds the receive area
from the communication
failure station
Clear
Clears the receive area
from the communication
failure station
Hold
Holds the receive area
from the communication
failure station
Remote
Remote
Remote
output
register
register
(RY)
(RWr)
(RWw)
*1
*3
Continue
Hold
*2
*1
*3
Continue
Hold
*3
Hold
*5
*5
Hold
Hold
Hold
Continue
Continue
Continue
Continue
Holds the
Continue
receive area
from the
communication
failure station
Continue
Holds the
Continue
receive area
from the
communication
failure station
Remote I/O station
Input
Output
Continue
All points off
*2
Continue
All points off
*3
Hold
By external
All points off
signals
By external
All points off
signals
Continue (Not
Continue (Not
affected by the
affected by the
communication
communication
status of the
status of the
remote device
remote device
station.)
station.)
Continue (Not
Continue (Not
affected by the
affected by the
communication
communication
status of the
status of the
intelligent
intelligent
device station.)
device station.)
4 FUNCTIONS
39