Item
Transmission format
Error control system
Connection cable
Maximum overall cable length (maximum
transmission distance)
Applicable CPU module
Applicable engineering tool
Number of connectable units
Number of occupied I/O points
*1 Refer toPage 20 Maximum Number of Connectable Modules (when operating as a master station) for the maximum number of
connected units of the CC-Link system when the master/intelligent device module is used as a master station.
*2 The remote I/O points that can be used in the CPU module varies depending on the number of input/output points of the expansion
device. For the limit of I/O points, refer to the following manual.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
*3 FX5-CNV-IFC or FX5-C1PS-5V is necessary to connected to the FX5UC CPU module.
*4 FX3U-16CCL-M cannot be used together when using FX5-CCL-MS as the master station.
*5 FX3U-64CCL cannot be used together when using FX5-CCL-MS as the intelligent device station.
Number of link points for each number of occupied stations
Shows the number of link points for each number of occupied stations.
Item
Number of link
1 Station
points for each
occupied
number of
occupied stations
2 Stations
occupied
3 Stations
occupied
4 Stations
occupied
The values in parenthesis are the number of available points when operating as an intelligent device station.
• When the number of occupied stations is 3 stations, single, double, or quadruple is selectable for the
extended cyclic setting of CC-Link Ver.2.
• When the number of occupied stations is 4 stations, single or double is selectable for the extended cyclic
setting of CC-Link Ver.2.
Description
HDLC compliance
16
12
5
+X
+X
+1)
CRC (X
Ver.1.10-compatible CC-Link dedicated cable
Depends on the transmission speed (Page 22 Maximum Overall Cable Length)
• FX5U CPU module (Ver. 1.050 or later)
*3
• FX5UC CPU module
(Ver. 1.050 or later)
GX Works3 (Ver. 1.035M or later)
One module of each station type can be connected to a CPU module.
*4
• Master station: 1 unit
• Intelligent device station: 1 unit
8 points
CC-Link Ver.1
Remote input/
32 points
output (RX, RY)
(16 points)
Remote register
4 points
(RWw)
Remote register
4 points
(RWr)
Remote input/
64 points
output (RX, RY)
(48 points)
Remote register
8 points
(RWw)
Remote register
8 points
(RWr)
Remote input/
96 points
output (RX, RY)
(80 points)
Remote register
12 points
(RWw)
Remote register
12 points
(RWr)
Remote input/
128 points
output (RX, RY)
(112 points)
Remote register
16 points
(RWw)
Remote register
16 points
(RWr)
*5
CC-Link Ver.2
Extended cyclic setting
Single
Double
32 points
32 points
(16 points)
(16 points)
4 points
8 points
4 points
8 points
64 points
96 points
(48 points)
(80 points)
8 points
16 points
8 points
16 points
96 points
160 points
(80 points)
(144 points)
12 points
24 points
12 points
24 points
128 points
224 points
(112 points)
(208 points)
16 points
32 points
16 points
32 points
Quadruple
Octuple
64 points
128 points
(48 points)
(112 points)
16 points
32 points
16 points
32 points
192 points
384 points
(176 points)
(368 points)
32 points
64 points
32 points
64 points
320 points
(304 points)
48 points
48 points
2 SPECIFICATIONS
2.3 Performance Specifications