Link device assignment
This section describes the RX, RY, RWr, or RWw assignment of program examples.
Remote net Ver.1 mode is used in this program example. When the remote net Ver.2 mode is used, the buffer
memory addresses of storage locations vary. ( Page 33 Remote net Ver.2 mode)
■RX/RY assignment
FX5U-32MR/ES
Master station
Buffer memory
Device
(remote input (RX))
X1000
Station
Station
No.1
No.1
X1017
(remote output (RY))
Y1000
Station
Station
No.1
No.1
Y1017
FX5U-32MR/ES
Master station
Device
Buffer memory address
Hexadecimal
X1000 to X1017
E0H
X1020 to X1037
E1H
Y1000 to Y1017
160H
Y1020 to Y1037
161H
The last 16 bits (1 word) in RX and RY cannot be used when using the master/intelligent device module as the
intelligent device station.
■RWr/RWw assignment
CPU module
Master station
Buffer memory
(remote register (RWr))
Device
W0
Station
Station
No.1
No.1
W3
(remote register (RWw))
W100
Station
Station
No.1
No.1
W103
FX5U-32MR/ES
Master Station
Device
Buffer memory address
Hexadecimal
W0
2E0H
W1
2E1H
W2
2E2H
W3
2E3H
W100
1E0H
W101
1E1H
W102
1E2H
W103
1E3H
Intelligent deivice station
Buffer memory
(remote input (RX))
E0H
E0H
Station
No.1
E1H
E1H
(remote output (RY))
160H
160H
Station
No.1
161H
161H
Slave station
Station
No.
Decimal
224
1
225
352
353
Intelligent device
station
Buffer memory
(remote register (RWr))
2E0H (736)
2E0H (736)
Station
No.1
2E3H (739)
2E3H (739)
(remote register (RWw))
1E0H (480)
1E0H (480)
Station
No.1
1E3H (483)
1E3H (483)
Slave station
Station
No.
Decimal
736
1
737
738
739
480
481
482
483
8.3 Example of Communications Between a Master Station and a Intelligent Device Station
FX5U-32MR/ES
Device
X1000
Station
No.1
X1017
Y1000
Station
No.1
Y1017
Module name
RX, RY
FX5-CCL-MS
RX0 to RXF
RX10 to RX1F (use prohibited because
they are system areas)
RY0 to RYF
RY10 to RY1F (use prohibited because
they are system areas)
CPU module
Device
W0
Station
No.1
W3
W100
Station
No.1
W103
Module name
RWr, RWw
FX5-CCL-MS
RWr0
RWr1
RWr2
RWr3
RWw0
RWw1
RWw2
RWw3
8 PROGRAMMING
87
8

Hide quick links: