Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 141

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Ver.2-compatible remote output (RY)
For the master station, output data to slave stations are stored.
For intelligent device stations, input data from the master station are stored.
• For intelligent device stations, regardless of the station No. of the station itself, stores data input from the
master station for the number of occupied stations from the station number 1 area.
• The last 16 bits (1 word) of RY cannot be used when using the master/intelligent device module as the
intelligent device station.
■Storage location for each station
The storage locations change depending on the number of occupied stations and extended cyclic settings in slave stations.
The storage locations for each station can be checked using Slave station offset, size information (Un\G1120 to Un\G1167).
(Page 135 Slave station offset, size information)
Master Station
FX5-CCL-MS
Address
Remote output (RY)
Station
4200H
RY F to RY 0
No.1
4201H
RY 1F to RY 10
Station
4202H
RY 2F to RY 20
No.2
4203H
RY 3F to RY 30
4204H
RY 4F to RY 40
4205H
RY 5F to RY 50
Station
·
·
No.3
4210H
RY 10F to RY 100
4211H
RY 11F to RY 110
4212H
RY 12F to RY 120
4213H
RY 13F to RY 130
Station
·
·
No.7
RY 1AF to RY 1A0
421AH
RY 1BF to RY 1B0
421BH
·
·
*1 The last 16 bits (1 word) of RY cannot be used when using the master/intelligent device module as the intelligent device station.
Remote I/O station
Remote I/O station
(Station No.: 1, number
(Station No.: 2, number
of occupied stations: 1)
of occupied stations: 1)
RY F to RY 0
RY 1F to RY 10
RY F to RY 0
RY 1F to RY 10
Intelligent device station
Intelligent device station
(Station No.: 3, number of
(Station No.: 7, number of
occupied stations: 4, extended
occupied stations: 3, extended
cyclic setting: Double)
cyclic setting: Double)
FX5-CCL-MS
Remote output (RY)
Address
RY F to RY 0
4200H
RY 1F to RY 10
4201H
·
·
420CH
RY CF to RY C0
*1
420DH
RY DF to RY D0
RY F to RY 0
RY 1F to RY 10
·
RY 8F to RY 80
RY 9F to RY 90
APPX
Appendix 4 Buffer Memory
A
139

Hide quick links:

Advertisement

Table of Contents
loading