Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 143

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Ver.2-compatible remote register (RWw)
For the master station, output data to slave stations are stored.
For intelligent device stations, input data from the master station are stored.
For intelligent device stations, regardless of the station No. of the station itself, stores data input from the
master station for the number of occupied stations from the station number 1 area.
■Storage location for each station
The storage locations change depending on the number of occupied stations and extended cyclic settings in slave stations.
The storage locations for each station can be checked using Slave station offset, size information (Un\G1248 to Un\G1295).
(Page 135 Slave station offset, size information)
Master Station
FX5-CCL-MS
Address
Remote register (RWw)
4400H
RWw 0
Station
4401H
RWw 1
No.1
4402H
RWw 2
4403H
RWw 3
4404H
RWw 4
4405H
RWw 5
·
·
Station
No.2
4420H
RWw 20
4421H
RWw 21
4422H
RWw 22
4423H
RWw 23
·
·
Remote device station initialization procedure registration execution individual info.
This area stores the execution progress of the remote device station initial setting procedure registration function.
Address
Remote device station initialization procedure registration execution individual info.
5C80H (23680)
Remote device station initialization procedure registration execution individual information (station number 1)
5C81H (23681)
Remote device station initialization procedure registration execution individual information (station number 2)
5C96H (23702)
Remote device station initialization procedure registration execution individual information (station number 23)
5C97H (23703)
Remote device station initialization procedure registration execution individual information (station number 24)
The following values are stored in the bits of Remote device station initialization procedure registration execution individual
information.
Bit
b15 to b8
b7 to b0
Remote device station
Intelligent device station
(Station No. 1,
(Station No. 4,
extended cyclic setting: single)
extended cyclic setting: Double)
FX5-CCL-MS
RWw 0
RWw 1
RWw 2
RWw 3
Remote register (RWw)
Description
Stores the next execution procedure number.
Stores the station number.
Address
RWw 0
4400H
RWw 1
4401H
·
·
RWw 1C
441CH
441DH
RWw 1D
RWw 1E
441EH
RWw 1F
441FH
Value
• 1 to 32 (In process)
• FFH (Completed)
(Default: 0)
1 to 24 (01H to 18H)
(Default: 0)
APPX
Appendix 4 Buffer Memory
A
141