Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 87

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

(0)
The data link status is checked.
(30)
When 'Remote device station initialization procedure registration instruction' (SB000D) is turned on, the initial setting is executed.
(62)
When 'Remote device station initial setting change' (X10) is turned on, the initial setting of AJ65VBTCU-68DAVN is changed.
(107) When 'Remote device station digital value change' (X 11) is turned on, the digital value of AJ65VBTCU-68DAVN is set.
(144) When 'Remote device station analog output enable' (X12) is turned on, analog values are output from AJ65VBTCU-68DAVN.
(181) If an error occurs in the AJ65VBTCU-68DAVN, an error code is stored in 'Error code' (D518).
After the cause of the error is eliminated and 'Remote device station error reset' (X13) is turned on, the error is reset.
(227) When 'Send data to remote IO flag' (X14)is turned on, remote output (RY10) of AJ65SBTC1-32DT is turned ON/OFF.
(258) When remote input (RX0) of AJ65SBTC1-32DT is turned ON/OFF, 'Receive data from remote IO flag'(Y11) is turned ON/OFF.
• When creating the programs of (30) to (58), refer to the manual for the remote device station used and
change the program as needed.
• The programs of (62) to (103) are needed only for the initial setting change.
8.2 Example of Communications Between a Master Station, a Remote Device Station and a Remote I/O Station