To assure the integrity of cyclic data in each slave station
One of the following actions assures the integrity of cyclic data in each slave station.
Note that data integrity is not assured across slave stations.
■Using the engineering tool
Set "Station-based Block Data Assurance" under "Supplementary Cyclic Settings" in "Application Settings" to "Enable." (
Page 71 Supplementary cyclic settings)
■Using a program
Interlock with RX and RY.
• Master station (station No. 0)
• Intelligent device stations (station No.1)
8.3 Example of Communications Between a Master Station and a Intelligent Device Station
8 PROGRAMMING