Error
Error details and causes
code
B309H
The station number of the connected module is duplicated
(including the number of occupied stations). However,
excluding duplication of the start station number.
B30AH
The station type differs between the mounted modules and
parameter settings.
B30BH
The module parameter details do not match the installation
status.
B30DH
A request, such as the temporary error invalid station
specification, line test request, or data link stop/restart
request, was issued before data link is started.
B30EH
Execution of a function that is started using SB, SW and
executable only on the master station was attempted on an
intelligent device station.
B30FH
System error
B310H
'Data link restart' (SB0000) was turned on specifying the
station that was performing data link.
B311H
'Data link stop' (SB0002) was turned on specifying the
station where data link had been stopped.
B316H
System error
B317H
System error
B31AH
The master station duplication error canceling instruction
was executed while data link had already been started.
B31BH
The 'Transmission speed test' (SB000B) was performed
during data link.
B31CH
System error
B31DH
System error
B31EH
Logging was started while logs were being deleted.
B31FH
Logs were deleted during logging.
B321H
System error
B322H
The logs were deleted during data link with "RAM + Flash
ROM" selected.
B323H
Although the logs had been set to be deleted with "RAM +
Flash ROM" selected, logging was started before deletion
of logs was complete.
B324H
Storing logs to the flash ROM was attempted when the
flash ROM was not ready for storage.
B326H
System error
B384H
System error
to
B388H
B38AH
System error
to
B38FH
B391H
System error
to
B399H
B39BH
System error
B39DH
System error
to
B39FH
B3A0H
An invalid mode has occurred in the master station and the
intelligent device station.
• The intelligent device station is in the remote net Ver.2
mode, and the master station is in the remote net Ver.1
mode.
B3A1H
System error
B3A3H
System error
B3A5H
System error
9 TROUBLESHOOTING
120
9.5 List of Error Codes
Corrective Action
Check the station number of the module. (including the
number of occupied stations)
• Correct the parameter.
• Set the parameters of the master station or intelligent
device station again, and reset the CPU module.
Correct the installation status or module parameters so that
both are matched.
Issue the request after the data link is started.
Execute the corresponding function from the master
station.
Please consult your local Mitsubishi representative.
Turn on 'Data link restart' (SB0000) specifying the station
where data link has been stopped using 'Data link stop'
(SB0002).
Turn on 'Data link stop' (SB0002) specifying the station
performing data link.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Do not execute the master station duplication error
cancellation instruction during data link.
Turn on 'Transmission speed test request' (SB000B) after
turning on 'Data link stop' (SB0002).
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Delete the logs then start logging.
Stop the logging then delete the logs.
Please consult your local Mitsubishi representative.
Terminate the data link then delete the logs.
Delete the logs again with "RAM + Flash ROM" selected.
Delete the logs with "RAM + Flash ROM" selected then
start logging, or start logging with "RAM" selected.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Correct the mode setting of the master station and
intelligent device station, and reset the CPU module.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Detailed
information

Hide quick links: