No.
Name
Description
SW0062
Module operating
Stores the module operation setting configured using the parameter.
status
b15b14b13
0
SW0064
Number of retries
Stores the set number of retries upon an abnormal response.
information
1 to 7 (time)
SW0065
Number of
Stores the set number of automatic return stations in one link scan.
automatic return
1 to 10 (station)
stations
SW0068
Parameter status
Stores whether the parameters have been correctly set.
of own station
0: Normal
Values other than 0: Error code (Page 118 List of Error Codes)
SW0069
Installation status
Stores whether unique station numbers have been assigned for modules and
whether parameter settings match with connected module status.
0: Normal
Values other than 0: Error code (Page 118 List of Error Codes)
Details are stored in SW0098, SW0099, SW009C, SW009D.
This item is checked only at link startup, and the result is stored.
SW006D
Maximum link
Stores the maximum link scan time.
scan time
(unit: 1 ms)
SW006E
Current link scan
Stores the current link scan time.
time
(unit: 1 ms)
SW006F
Minimum link scan
Stores the minimum link scan time.
time
(unit: 1 ms)
SW0070
Total number of
Stores the end station number set using the parameter.
stations
1 to 24 (station)
SW0071
Maximum
Stores the maximum station number during data link (station number set using
communication
the station number setting switches).
station number
1 to 24 (station)
Reserved stations are excepted.
SW0072
Number of
Stores the number of modules performing data link.
connected
Reserved stations are excepted.
modules
SW0074,
Reserved station
Stores the reserved station setting status.
SW0075
specification
0: A station other than a reserved station
status
1: Reserved Station
SW0074
SW0075
Only the bit corresponding to the start station number turns on.
The station with the end station number and stations later than that are
excepted.
The use of b8 to b15 of SW0075 is prohibited.
b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
0
0
0
0
0
0
0
Input Data from Data Link Faulty Station
0: Clear
1: Hold
Number of occupied stations
00: 1 station occupied
10: 2 station occupied
11: 3 station occupied
01: 4 station occupied
Output data setting in case of CPU STOP
0: Send ouput data
1: Send 0 data
Extended cyclic setting
00: Single
01: Double
10: Quadruple
11: Octuple
Station-based block data assurance
0: Disable
1: Enable
b15
b14
to
b8
16
15
to
9
-
-
-
-
1 to 24 in the table indicate station numbers.
b7
to
b2
b1
b0
8
to
3
2
1
24
to
19
18
17
Appendix 6 List of Link Special Register (SW) Areas