Ver.2-compatible remote input (RX) and Ver.2-compatible remote output (RY)
This buffer memory area is used when the remote net Ver.2 mode is selected.
In the remote net Ver.2 mode, data are stored in the remote input (RX) and remote output (RY) of all slave stations. (including
Ver.1-compatible slave stations)
Page 33 Remote net Ver.2 mode
■Ver.2-compatible remote input (RX)
For the master station, input data from slave stations are stored.
For intelligent device stations, output data to the master station are stored.
• For intelligent device stations, regardless of the station No. of the station itself, store data output to the
master station for the number of occupied stations from the station number 1 area.
• The last 16 bits (1 word) of RX cannot be used when using the master/intelligent device module as the
intelligent device station.
■Storage location for each station
The storage locations change depending on the number of occupied stations and extended cyclic settings in slave stations.
The storage locations for each station can be checked using Slave station offset, size information (Un\G992 to Un\G1039).
(Page 135 Slave station offset, size information)
Master Station
FX5-CCL-MS
Address
Remote input (RX)
Station
4000H
RX F to RX 0
No.1
4001H
RX 1F to RX 10
Station
4002H
RX 2F to RX 20
No.2
4003H
RX 3F to RX 30
4004H
RX 4F to RX 40
4005H
RX 5F to RX 50
Station
·
·
No.3
4010H
RX 10F to RX 100
4011H
RX 11F to RX 110
RX 12F to RX 120
4012H
4013H
RX 13F to RX 130
Station
·
·
No.7
401AH
RX 1AF to RX 1A0
401BH
RX 1BF to RX 1B0
·
·
*1 The last 16 bits (1 word) of RX cannot be used when using the master/intelligent device module as the intelligent device station.
APPX
138
Appendix 4 Buffer Memory
Remote I/O station
Remote I/O station
(Station No.: 1, number
(Station No.: 2, Number
of occupied stations: 1)
of occupied stations: 1)
RX F to RX 0
RX 1F to RX 10
RX F to RX 0
RX 1F to RX 10
Intelligent device station
(Station No.: 3, Number of
occupied stations: 4, extended
cyclic setting: Double)
FX5-CCL-MS
Remote input (RX)
Address
RX F to RX 0
4000H
RX 1F to RX 10
4001H
·
·
RX CF to RX C0
400CH
400DH
*1
RX DF to RX D0
Intelligent device station
(Station No.: 7, Number of
occupied stations: 3, extended
cyclic setting: Double)
RX F to RX 0
RX 1F to RX 10
·
RX 8F to RX 80
RX 9F to RX 90