9 TROUBLESHOOTING
112
9.4 Troubleshooting by Symptom
Description
Initial setting
Has the initial setting completed?
Has the remote device station
initialization procedure registration
completed?
Is the initial setting for the remote
device station correct?
Has the initialize setting been
enabled?
Description
Refresh data
Has the link refresh been correctly
area
set? (RX, RY, RWw, RWr, SB,
SW)
Is the buffer memory area
accessed correctly? (RX, RY,
RWw, RWr, SB, SW)
Parameter
Is a station to which reading/
Setting
writing cannot be performed
specified as a reserved station?
Parameter
Do the parameter settings match
Setting
with the status of the connected
modules?
Parameter
Do the parameter settings match
Setting
with the status of the connected
modules?
Check method
Were RYn18 (Initial data
processing completion flag) and
RYn19 (Initial data setting request
flag) turned on and off?
• Check if 'Remote device station
initialization procedure
registration instruction'
(SB000D) is turned off.
• Check 'Remote device station
initialization procedure
registration instruction result'
(SW005F).
• Check the parameter.
• Check the program.
Check if 'Remote device station
initialization procedure registration
instruction' (SB000D) has been
turned on using a program.
Check method
Check if no device overlaps with
ones used in programs or in other
networks.
Check if no device in the master
station overlaps with ones used in
programs or in other networks.
Check if the bit corresponding to
the faulty station is not "1" in
'Reserved station specification
status' (SW0074, SW0075).
Check if a remote I/O station is
connected to the corresponding
station number.
Check if a module with the small
number of occupied stations is not
connected to the corresponding
station number.
Corrective Action
Perform the initial data
processing.
Change the registration.
Correct the remote device station
initial setting.
Turn on 'Remote device station
initialization procedure registration
instruction' (SB000D) using a
program and check that the
initialize setting is enabled.
Corrective Action
Set the devices so that they do not
overlap with ones used in
programs and in other networks.
• Access the correct buffer
memory area in the master
station.
• Set the devices so that they do
not overlap with ones used in
programs.
Cancel the reserved station
setting.
Match the model set by the
parameter with that of the
connected module.
Match the number of occupied
stations set by the parameter with
that of the connected module.