Connect AC Power Cords
The SP runs on the 3.3V standby voltage. As soon as power is connected, the SP powers on,
runs diagnostics, and initializes the Oracle ILOM firmware.
Note -
messages.
1.
Ensure that you have a connection to the SP.
See
"Cable the SP" on page
Note -
AC power cord is connected to the power source. By having a connection to the SP, you can
view and interact with the initialization process.
2.
(Optional for AC models) Connect the chassis ground studs to earth ground.
See
"Connect the Chassis Ground Wire" on page
Route the AC power cords from the AC power source (for example, a power
3.
distribution unit) to the rear of the server.
Use two power connections on separate circuits for redundancy.
74
Netra Server X5-2 Installation Guide • June 2016
If you do not connect a serial terminal or a terminal emulator, you will not see the system
64.
The server goes into Standby mode and the service processor initializes as soon as the
76.