Lenovo HX1310 Installation And Service Manual page 305

Converged systems converged hx series
Table of Contents

Advertisement

Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Voltage
SNMP Trap ID
13
CIM Information
Prefix: PLAT ID: 0476
User Response
Replace the system battery.
• 80010202-0701ffff : Numeric sensor [NumericSensorElementName] going low (lower critical) has
asserted. (CMOS Battery)
This message is for the use case when an implementation has detected a Lower Critical sensor going
low has asserted.
May also be shown as 800102020701ffff or 0x800102020701ffff
Severity
Error
Serviceable
Yes
Automatically notify support
Yes
Alert Category
Critical - Voltage
SNMP Trap ID
1
CIM Information
Prefix: PLAT ID: 0480
User Response
If the specified sensor is CMOS battery, replace the system battery. If the specified sensor is Planar
3.3V or Planar 5V, (trained technician only) replace the system board. If the specified sensor is Planar
12V, complete the following steps until the problem is solved:
1. Check power supply n LED.
2. Remove the failing power supply.
3. Follow actions in "Power Problems and Solving Power Problems".
4. (Trained technician only) Replace the system board. (n = power supply number)
SysBrd 12V : SysBrd 3.3V : SysBrd 5V :
Appendix A. Integrated management module 2.1 (IMM2.1) error messages
291