ABB Relion 630 Series RET630 Product Manual

ABB Relion 630 Series RET630 Product Manual

Transformer protection and control

Advertisement

®
Relion
630 series
Transformer Protection and Control
RET630
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 630 Series RET630

  • Page 1 ® Relion 630 series Transformer Protection and Control RET630 Product Guide...
  • Page 2: Table Of Contents

    15. Current circuit supervision........14 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    The pre-defined networks. RET630 is a member of ABB’s configurations can be used as such or easily ® adapted or extended with freely selectable...
  • Page 4 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 GUID-EBE462A5-7366-467A-BA18-583E75428EDB V2 EN Figure 1. RET630 and REF630 IEDs applied for the incoming feeder and primary switchgear in a double busbar arrangement. The RET630 with preconfiguration A is used for protection and control of the power transformer, the REF630 with preconfiguration B protects and controls the outgoing feeder and the REF630 with preconfiguration D is used for the bus sectionalizer.
  • Page 5: Preconfigurations

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 configuration of the LEDs and function 3. Preconfigurations buttons, and adaptation of the default single- line diagram. The 630 series IEDs are offered with optional In addition, the adaptation of the factory-made preconfigurations for various preconfiguration always includes applications.
  • Page 6 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 2. Functions used in preconfigurations. Column 'n' shows the total number of available function instances regardless of the preconfiguration selected. Functionality Protection Three-phase non-directional overcurrent, low stage (LV side) Three-phase non-directional overcurrent, low stage (HV side) Three-phase non-directional overcurrent, high stage (LV side) Three-phase non-directional overcurrent, high stage (HV side)
  • Page 7 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 2. Functions used in preconfigurations. Column 'n' shows the total number of available function instances regardless of the preconfiguration selected., continued Functionality Frequency gradient Overfrequency Underfrequency Overexcitation protection Three-phase underimpedance protection Transformer differential protection for two-winding transformers Circuit-breaker failure (HV side)
  • Page 8 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 2. Functions used in preconfigurations. Column 'n' shows the total number of available function instances regardless of the preconfiguration selected., continued Functionality Circuit breaker condition monitoring (HV side) Fuse failure supervision Current circuit supervision (LV side) Current circuit supervision (HV side)
  • Page 9: Protection Functions

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 2. Functions used in preconfigurations. Column 'n' shows the total number of available function instances regardless of the preconfiguration selected., continued Functionality Binary receive Double point receive Interlock receive Integer receive Measured value receive...
  • Page 10 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 GUID-FD724103-823D-4443-ACAE-412BB7906240 V2 EN Figure 2. Protection function overview of preconfiguration A...
  • Page 11: Control

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 GUID-2825EF67-84B7-4039-B34E-8A0BA237AE1E V2 EN Figure 3. Protection function overview of preconfiguration B Further, the IED incorporates a synchro- 5. Control check function to ensure that the voltage, phase angle and frequency on either side of an open circuit breaker satisfy the conditions The IED incorporates local and remote for safe interconnection of two networks.
  • Page 12: Measurement

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 power transformer using the raise and lower The values measured are accessed locally via signals to the on-load tap changer. the front-panel user interface of the IED or remotely via the communication interface of The automatic voltage regulation can be used the IED.
  • Page 13: Event Log

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 9. Event log 11. Circuit-breaker monitoring The IED features an event log which enables logging of event information. The event log The condition monitoring functions of the can be configured to log information IED constantly monitors the performance and according to user pre-defined criteria the condition of the circuit breaker.
  • Page 14: Fuse Failure Supervision

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 User Administrator. The user group 14. Fuse failure association for each individual user enables supervision the use of the IED according to the profile of the user group. The fuse failure supervision detects failures between the voltage measurement circuit and the IED.
  • Page 15 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 via the RTD or mA inputs and provides four mA outputs can be used for transferring mA outputs. The RTD and mA inputs can for freely selectable measured or calculated instance be used for measuring oil analog values to devices provided with mA temperature at the bottom and top of the...
  • Page 16: Communication

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 5. Binary input/output options for 6U variants Binary I/O options Binary input configuration Default With one optional binary I/O module With two optional binary I/O modules With three optional binary I/O modules With four optional binary I/O modules...
  • Page 17 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 The IED supports the following time With special time synchronization wiring: synchronization methods with a • IRIG-B (Inter-Range Instrumentation Group timestamping resolution of 1 ms: - Time Code Format B) Ethernet communication based: IEC 60870-5-103 serial communication has a •...
  • Page 18: Technical Data

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 19. Technical data Table 7. Dimensions Description Value Width 220 mm Height 177 mm (4U) 265.9 mm (6U) Depth 249.5 mm Weight box 6.2 kg (4U) 5.5 kg (6U) Weight LHMI 1.0 kg (4U) 1) Without LHMI...
  • Page 19 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 9. Energizing inputs Description Value Rated frequency 50/60 Hz Operating range Rated frequency ± 5 Hz Current inputs Rated current, I 0.1/0.5 A 1/5 A Thermal withstand capability: •...
  • Page 20 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 11. RTD inputs Description Value Supported RTD sensor 100 Ω platinum TCR 0.00385 inputs (DIN 43760) 250 Ω platinum TCR 0.00385 100 Ω nickel TCR 0.00618 (DIN 43760) 120 Ω...
  • Page 21 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 11. RTD inputs, continued Description Value mA inputs Supported current range -20 mA … +20 mA Current input impedance 100 Ω ± 0.1% Operation accuracy ± 0.1% ± 20 ppm per °C of full- Ambient scale temperature...
  • Page 22 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 14. Power output relays with TCS function Description Value Rated voltage 250 V DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit ≤1 A/≤0.3 A/≤0.1 A...
  • Page 23 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 18. X4/IRIG-B interface Type Protocol Cable Screw terminal, pin IRIG-B Shielded twisted pair cable row header Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire (Alpha 6222-6230) Table 19.
  • Page 24 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 23. Environmental tests Description Type test value Reference Dry heat test (humidity <50%) • 96 h at +55ºC IEC 60068-2-2 • 16 h at +85ºC Cold test •...
  • Page 25 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 24. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst IEC 61000-4-18 disturbance test IEC 60255-22-1, level 3 • Common mode 2.5 kV •...
  • Page 26 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 24. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity Binary inputs only IEC 60255-22-7, class A test IEC 61000-4-16 300 V rms • Common mode 150 V rms •...
  • Page 27 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 25. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 IEC 60255-27 • Test voltage 2 kV, 50 Hz, 1 min 500 V, 50 Hz, 1 min, communication Impulse voltage test: IEC 60255-5...
  • Page 28 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 28. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007) Table 29. RoHS compliance Description Complies with RoHS directive 2002/95/EC...
  • Page 29 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Protection functions Table 30. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy At the frequency f = f PHLPTOC ±1.5% of the set value or ±0.002 x I PHHPTOC ±1.5% of set value or ±0.002 x I (at currents in the range of 0.1…10 x I...
  • Page 30 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 31. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Function Value (Range) Step Start Value PHLPTOC 0.05...5.00 pu 0.01 PHHPTOC 0.10...40.00 pu 0.01 PHIPTOC 0.10...40.00 pu 0.01 Time multiplier PHLPTOC 0.05...15.00...
  • Page 31 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 32. Three-phase directional overcurrent protection (DPHxPDOC) Characteristic Value Operation accuracy At the frequency f = f DPHLPDOC Current: ±1.5% of the set value or ±0.002 x I Voltage: ±1.5% of the set value or ±0.002 x U Phase angle:...
  • Page 32 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 33. Three-phase directional overcurrent protection (DPHxPDOC) main settings Parameter Function Value (Range) Step Start value DPHLPDOC 0.05...5.00 pu 0.01 DPHHPDOC 0.05...5.00 pu 0.01 Time multiplier DPHxPDOC 0.05...15.00 0.05 Operate delay time DPHxPDOC...
  • Page 33 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 34. Non-directional earth-fault protection (EFxPTOC) Characteristic Value Operation accuracy At the frequency f = f EFLPTOC ±1.5% of the set value or ±0.001 x I EFHPTOC ±1.5% of set value or ±0.002 x I (at currents in the range of 0.1…10 x I EFIPTOC ±5.0% of the set value...
  • Page 34 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 35. Non-directional earth-fault protection (EFxPTOC) main settings Parameter Function Value (Range) Step Start value EFLPTOC 0.010...5.000 pu 0.005 EFHPTOC 0.10...40.00 pu 0.01 EFIPTOC 0.10...40.00 pu 0.01 Time multiplier EFLPTOC 0.05...15.00 0.05...
  • Page 35 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 36. Directional earth-fault protection (DEFxPDEF) Characteristic Value Operation accuracy At the frequency f = f DEFLPDEF Current: ±1.5% of the set value or ±0.002 x I Voltage ±1.5% of the set value or ±0.002 x U Phase angle: ±2°...
  • Page 36 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 37. Directional earth-fault protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start Value DEFLPDEF 0.010...5.000 pu 0.005 DEFHPDEF 0.10...40.00 pu 0.01 Directional mode DEFLPDEF and 1=Non-directional DEFHPDEF 2=Forward 3=Reverse...
  • Page 37 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 38. Stabilized restricted earth-fault protection (LREFPNDF) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × I = 2.0 × set Typical 18 ms (±5 ms) 1)2) Start time...
  • Page 38 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 40. High-impedance based restricted earth-fault protection (HREFPDIF) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × I = 2.0 × set Typical 22 ms (±5 ms) 1)2) Start time...
  • Page 39 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 42. Negative-sequence overcurrent protection (NSPTOC) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × I = 2 × set Start Typical 23 ms (±15 ms) 1)2) Start time...
  • Page 40 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 44. Three-phase thermal overload protection for transformers (T2PTTR) Characteristic Value Operation accuracy At the frequency f = f Current measurement: ±1.5% of the set value or ±0.002 x I (at currents in the range of 0.01...4.00 x I ±2.0% or ±1000 ms...
  • Page 41 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 47. Three-phase current inrush detection (INRPHAR) main settings Parameter Function Value (Range) Step Start value (Ratio of INRPHAR 5...100 % the 2nd to the 1st harmonic leading to restraint) Operate delay time INRPHAR...
  • Page 42 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 49. Transformer differential protection for two-winding transformers (TR2PTDF) main settings Parameter Function Value (Range) Step Restraint mode TR2PTDF 2.h & 5.h & wav Waveform 2.h & waveform 5.h &...
  • Page 43 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 50. Three-phase overvoltage protection (PHPTOV) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × U = 2.0 x set Start Typical 17 ms (±15 ms) 1)2) Start time...
  • Page 44 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 52. Three-phase undervoltage protection (PHPTUV) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × U = 0.9 x set Typical 24 ms (±15 ms) 1)2) Start time...
  • Page 45 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 54. Positive-sequence overvoltage protection (PSPTOV) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 x U = 1.1 x set 1)2) Start time Fault...
  • Page 46 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 56. Positive-sequence undervoltage protection (PSPTUV) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × U = 0.9 x set Start Typical 28 ms (±15 ms) 1)2) Start time...
  • Page 47 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 58. Negative-sequence overvoltage protection (NSPTOV) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × U = 1.1 x set Typical 29 ms (±...
  • Page 48 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 60. Residual overvoltage protection (ROVPTOV) Characteristic Value Operation accuracy At the frequency f = f ±1.5% of the set value or ±0.002 × U = 1.1 x set Typical 27 ms (±...
  • Page 49 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 63. Frequency gradient protection (DAPFRC) main settings Parameter Function Value (Range) Step Start value DAPFRC -10.00...10.00 Hz/s 0.01 Operate delay time DAPFRC 0.120...60.000 s 0.001 Table 64. Overfrequency protection (DAPTOF) Characteristic Value Operation accuracy...
  • Page 50 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 67. Underfrequency protection (DAPTUF) main settings Parameter Function Value (Range) Step Start value DAPTUF 35.0...64.0 Hz Operate delay time DAPTUF 0.170...60.000 s 0.001 Table 68. Overexcitation protection (OEPVPH) Characteristic Value Operation accuracy...
  • Page 51 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 70. Three-phase underimpedance protection (UZPDIS) Characteristic Value Operation accuracy Depending on the frequency of the current and voltage measured f = fn ±2 Hz ±3.0% of the set value or ±0.2% x Zb Start time Typical 25 ms (±15 ms) Reset time...
  • Page 52 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 73. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function Value (Range) Step Current value CCBRBRF 0.05...1.00 pu 0.05 (Operating phase current) Current value Res CCBRBRF 0.05...1.00 pu 0.05 (Operating residual current)
  • Page 53 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 76. Operation characteristics Parameter Values (Range) Operating curve type 1=ANSI Ext. inv. 2=ANSI Very. inv. 3=ANSI Norm. inv. 4=ANSI Mod inv. 5=ANSI Def. Time 6=L.T.E. inv. 7=L.T.V. inv. 8=L.T.
  • Page 54 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 78. Tap changer control with voltage regulator (OLATCC) Characteristic Value Depending on the frequency of the current measured: fn ±2 Operation accuracy Differential voltage Ud ± 1.0% of the measured value or ±...
  • Page 55 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 79. Voltage regulator (OLATCC) main settings Parameter Function Values (Range) Step Operation mode OLATCC Manual Auto single Auto parallel Input control Custom Man blocking OLATCC Custom disabled OC, UV OC, EXT UV, EXT...
  • Page 56 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 79. Voltage regulator (OLATCC) main settings, continued Parameter Function Values (Range) Step Load phase angle OLATCC -89 - 89 Control delay time 1 OLATCC 1.0 - 300.0 Control delay time 2 OLATCC 1.0 - 300.0...
  • Page 57 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 82. Current circuit supervision (CCRDIF) Characteristic Value < 30 ms Operate time 1) Including the delay of the output contact. Table 83. Current circuit supervision (CCRDIF) main settings Parameter Function Values (Range)
  • Page 58 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Measurement functions Table 88. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy At the frequency f = f ±0.5% or ±0.002 x I (at currents in the range of 0.01...4.00 x I Suppression of harmonics DFT: -50 dB at f = n x f , where n = 2, 3, 4, 5,...
  • Page 59 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 92. Residual voltage measurement (RESVMMXU) Characteristic Value Operation accuracy At the frequency f = f ±0.5% or ±0.002 × U Suppression of harmonics DFT: -50 dB at f = n × f , where n = 2, 3, 4, 5, …...
  • Page 60: Front Panel User Interface

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 programmable function buttons with LED 20. Front panel user indicators. The 15 programmable alarm LEDs interface can indicate a total of 45 alarms. The local HMI offers full front-panel user-interface functionality with menu navigation, menu The 630 series IEDs can be ordered with an views and operational data.
  • Page 61 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 To ensure grounding of the RTD channels, a For further information regarding different separate cable shield rail is included in the mounting options see the installation manual. IED delivery when the optional RTD/mA module is ordered.
  • Page 62: Selection And Ordering Data

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 labels, one label for each module in the IED. 22. Selection and The module labels state the type and serial ordering data number of each module. The order number consists of a string of codes generated from the hardware and The IED type and serial number label software modules of the IED.
  • Page 63 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 T B T B A B A E B B B Z EA N A X B DESCRIPTION numerical REF protection N = None Pre- Available analog Available binary inputs/ conf.
  • Page 64 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 T B T B A B A E B B B Z E A N A X B DESCRIPTION Communication serial Communication Ethernet Ethernet 100BaseFX (LC) Ethernet 100BaseTX (RJ-45) Communication protocol IEC 61850 IEC 61850 and DNP3 TCP/IP...
  • Page 65 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 T B T B A B A E B B B Z E A D A X B DESCRIPTION Language English and Chinese Front panel Integrated local HMI Detached local HMI, 1 m cable Detached local HMI, 2 m cable Detached local HMI, 3 m cable...
  • Page 66: Accessories

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Example code: T B T B A B A E B B B Z E A N A X B Your ordering code: Digit (#) 10 11 12 13 14 15 16 17 18 ...
  • Page 67: Tools

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 97. Test switch mounting accessories Item Order number 19" rack mounting kit for one RTXP8 test switch (the test switch is 1KHL400465R0001 not included in the delivery) 19"...
  • Page 68 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 When the web-browser based user interface The IED connectivity package is a collection is used, the IED can be accessed either of software and specific IED information, locally or remotely using a web browser (IE which enable system products and tools to 7.0 or later).
  • Page 69: Supported Abb Solutions

    By utilizing the Connectivity Packages the IEDs can be readily configured via the PCM600 ABB’s 630 series protection and control IEDs Protection and Control IED Manager and together with the COM600 Station integrated with the COM600 Station...
  • Page 70 COM600 features a web- and management systems such as browser based HMI providing a customizable MicroSCADA Pro and System 800xA. graphical display for visualizing single line Table 102. Supported ABB solutions Product Version Station Automation COM600 3.3 or later MicroSCADA Pro 9.2 SP1 or later...
  • Page 71: Terminal Diagrams

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 27. Terminal diagrams GUID-3901C29E-BCA6-44AE-B6BC-B2FA10958F19 V1 EN Figure 10. Terminal diagram for RET630...
  • Page 72 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 GUID-5E27DD50-FD15-4824-BDFB-DD52E29730EA V1 EN Figure 11. 630 series BIO module option...
  • Page 73 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 GUID-CB7B1CF8-A0E4-42F5-998C-701641515127 V1 EN Figure 12. 630 series RTD module option...
  • Page 74: References

    28. References the web page contains the latest product documentation, such as technical reference manual, installation manual, operators www.abb.com/substationautomation manual, etc. The selection tool on the web portal offers you information about the page helps you find the documents by the distribution automation product and service document category and language.
  • Page 75: Functions, Codes And Symbols

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 29. Functions, codes and symbols Table 103. Functions included in RET630 Functionality IEC 61850 IEC 60617 ANSI Protection Three-phase non-directional PHLPTOC 3I> 51P-1 overcurrent, low stage Three-phase non-directional PHHPTOC 3I>>...
  • Page 76 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 103. Functions included in RET630, continued Functionality IEC 61850 IEC 60617 ANSI Residual overvoltage ROVPTOV U0> Frequency gradient DAPFRC df/dt> Overfrequency DAPTOF f> Underfrequency DAPTUF f< Overexcitation protection OEPVPH U/f>...
  • Page 77 Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 103. Functions included in RET630, continued Functionality IEC 61850 IEC 60617 ANSI Circuit-breaker condition SSCBR CBCM CBCM monitoring (HV side) Fuse failure supervision SEQRFUF FUSEF Current circuit supervision CCRDIF MCS 3I MCS 3I...
  • Page 78: Document Revision History

    Transformer Protection and Control 1MRS756978 D RET630 Product version: 1.1 Issued: 2011-05-18 Table 103. Functions included in RET630, continued Functionality IEC 61850 IEC 60617 ANSI Double point receive GOOSEDPRCV Interlock receive GOOSEINTLKRCV Integer receive GOOSEINTRCV Measured value receive GOOSEMVRCV Single point receive GOOSESPRCV 30.
  • Page 80 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...