A.5 Bypass Options
This following configurations are available for the Z1000 Bypass.
u

Option B

Three-contactor bypass: Isolates the drive circuit by adding a separate drive input contactor.
u

Option D

Ethernet/IP option.
u

Option M

Motor Circuit Protector (MCP)/Disconnect: Replaces the standard input disconnect switch and provides short circuit protection
integral with the drive and bypass package. The MCP includes a feature to padlock the operator mechanism through the door.
Without this option, short circuit protection must be provided by others on the input side of the drive and bypass.
u

Option G

Drive Input Disconnect Switch: Provides a disconnect means for the input side of the Drive, for Drive isolation capability
during bypass operation. This disconnect is located inside the enclosure with an integral operating handle.
u

Option L

Serial Communication, Echelon LonWorks: An isolated circuit board provides LonTalk protocol for network communication
to a BAS. This option plugs into the CN5 connection on the bypass control circuit board.
u

Option W

Custom Nameplate: Provides a custom nameplate for placement on the front of the Z1000 Bypass.
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual