YASKAWA Z1000 Technical Manual page 197

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Input terminals A1 and A2 can accept a current input signal. Refer to
Table 5.27 Analog Input Settings for Frequency Reference Using a Current Signal
Signal
Terminal
Level
4 to 20 mA
A1
0 to 20 mA
4 to 20 mA
A2
0 to 20 mA
Figure 5.55 Setting the Frequency Reference as a Current Signal to Terminal A2
Switching between Main/Auxiliary Frequency References
The frequency reference input can be switched between the analog terminals A1 and A2 using multi-speed inputs.
Setting 2: BACnet, MEMOBUS/Modbus, P1, or N2 Communications
This setting requires entering the frequency reference via the RS-485 serial communications port (control terminals TXRX+
and TXRX-).
Setting 3: Option Card
This setting requires entering the frequency reference via an option board plugged into connector CN5 on the bypass control
board. Consult the option card manual for instructions on integrating the drive with the communication system.
n
Z1-08: Run Command Select
Determines the source of the Auto Mode RUN command used by the Bypass Controller.
No.
Z1-08
Setting 0: HOA Keypad
Setting 1: Bypass Controller Digital Input
This setting requires entering the Run command via the digital input terminals.
Setting 2: BACnet or MEMOBUS/Modbus Communications
This setting requires entering the Run command via serial communications by connecting the RS-485 serial communication
cable to control terminals TXRX+ and TXRX- on the terminal block.
380
for instructions.
Setting 3: Option Card
This setting requires entering the Run command via the communication option board by plugging a communication option
board into the CN5 port on the control PCB. Refer to the option card manual for instructions on integrating the bypass into
the communication system.
n
Z1-09: HAND Mode Drive Speed Reference
The speed reference used when the Drive is running in HAND mode.
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Parameter Settings
Signal Level
Function
Selection
Selection
H3-01 = 2
H3-02 = 0
(Frequency
H3-01 = 3
Reference Bias)
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-09 = 3
Jumper S1
Terminal A1/A2
Voltage/Current
Selection
V
I
A1 A2
0 or 4 to 20 mA
Name
Run Command Select
Table 5.27
to set terminals A1 and A2 for current input.
Gain
H3-03
H3-11
Drive
V
I
A1 A2
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
AC Analog input common
Refer to MEMOBUS/Modbus Configuration on page
5.15 Z: Bypass Parameters
Notes
Bias
H3-04
Make sure to set Jumper S1 on the
control board to "I" for current
input.
H3-12
Setting Range
1 to 3
5
Default
1
197