YASKAWA Z1000 Technical Manual page 215

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

n
Z3-03: Serial Communications Baud Rate Select
Selects the bypass serial communications speed.
Selecting settings 0, 1, or 2 will trigger an oPE29 error when using BACNet communication (Z3-01 = 3) in bypass controller
software versions VST800400 and later.
No.
Z3-03
Setting 0: 1200 bps
Setting 1: 2400 bps
Setting 2: 4800 bps
Setting 3: 9600 bps
Setting 4: 19200 bps
Setting 5: 38400 bps
Setting 6: 57600 bps
Setting 7: 76800 bps
Setting 8: 115200 bps
n
Z3-04: Serial Communications Parity Select
Selects the bypass serial communications parity. This setting is ignored when BACnet protocol is selected.
No.
Z3-04
Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity
n
Z3-05: Serial Communications Fault Select
Selects the action to take when a serial communications fault is detected. A serial communications fault is detected when after
last communicating, no communications occurs within the time set to Z3-06.
No.
Z3-05
Setting 0: Ignore
Setting 1: Alarm Only
Setting 2: Fault with EF0
An EF0 fault will be sent to the drive.
Setting 3: Fault with EF0 and Open Contactors
An EF0 fault will be sent to the drive and the bypass contactor (K3) will be opened.
Setting 4: Alarm and run at preset speed set in Z3-10
Display AL14 alarm on operator.
n
Z3-06: Serial Communications Fault Time Select
Sets the time allowed to elapse since receiving serial communications before triggering a communications fault.
A value of 0.0 means to never time out.
No.
Z3-06
n
Z3-07: Serial Communications Receive to Transmit Wait Time
Sets the time to delay a serial communications response to a serial communications command.
No.
Z3-07
Serial Communications Receive to Transmit Wait Time
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Name
Serial Communications Baud Rate Select
Name
Serial Communications Parity Select
Name
Serial Communications Fault Select
Name
Serial Communications Fault Time Select
Name
5.15 Z: Bypass Parameters
Setting Range
0 to 8
Setting Range
0 to 2
Setting Range
0 to 4
Setting Range
0.0 s to 99.9 s
Setting Range
0 to 99 ms
Default
3
Default
0
Default
1
5
Default
2.0 s
Default
5 ms
215