YASKAWA Z1000 Technical Manual page 414

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

E.4 APOGEE FLN Point List Summary
Point
Point
No.
Type
{28}
LDI
{29}
LDO
30
LAO
31
LAO
32
LAO
33
LDO
<4>
LDO
35
36
LAO
37
LAO
38
LAO
39
LAO
{40}
LDI
{41}
LDI
{42}
LDI
{43}
LDI
<5>
LDO
{44}
<5>
LDO
{45}
<5>
LDO
{46}
<5>
LDO
{47}
<5>
LDO
{48}
49
LAO
50
LAO
51
LAO
52
LAO
53
LAO
54
LAO
55
LAO
56
LAO
57
LAO
{58}
LDI
{59}
LDI
414
Factory
Engr. Units
Point Name
Default
(SI Units)
LOC.REM
REMOTE
MON
DAY.NGT
DAY
CURRENT
0
LMT
ACCEL
0
TIME
DECEL
0
TIME
LOCK
UNLOCK
PANEL
RUN
STOP
ENABLE
STALL PRE
90
RN
STALL PRE
120
AC
FREQ UP
100
LIM
FREQ LOW
0
LIM
MULTI OUT
OFF
1
MULTI OUT
OFF
2
MULTI OUT
OFF
3
SAFETY
OFF
ILOCK
MF INP 1
OFF
MF INP 2
OFF
MF INP 3
OFF
MF INP 4
OFF
MF INP 5
OFF
JUMP FREQ
0
1
JUMP FREQ
0
2
JUMP FREQ
0
3
JUMP FREQ
0
BW
NUM
0
AUTOSTRT
POWER
0.1
LOSS RT
RUN OP
1
MODE
REF OP
1
MODE
OPER DISP
0
MD
MF IN 1
OFF
MON
MF IN 2
OFF
MON
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Slope
(SI Units)
(SI Units)
(SI Units)
1
1
AMPS (A)
<1>
0.01/0.1
SEC
0.1
SEC
0.1
1
1
PCT
1
PCT
1
PCT
0.1
PCT
0.1
1
1
1
1
1
1
1
1
1
HZ
0.1
HZ
0.1
HZ
0.1
HZ
0.1
1
SEC
0.1
1
1
1
1
1
Intercept
On
Text
0
LOCAL
REMOTE
0
NGT
0
0
0
0
LOCK
UNLOCK
0
ENABLE
30
0
0
0
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
0
0
0
0
0
0
0
0
0
ON
0
ON
Off
Z1000
Text
Parameter
UB-05
DAY
E2-01
C1-01
C1-02
STOP
Bypass DI-2
L3-06
L3-02
d2-01
d2-02
UB-03 (Bit 6)
OFF
Bypass DO-7
UB-03 (Bit 7)
OFF
Bypass
DO-08
UB-03 (Bit 8)
OFF
Bypass DO-9
OFF
UB-05 (Bit 7)
OFF
Bypass DI-3
OFF
Bypass DI-4
OFF
Bypass DI-5
OFF
Bypass DI-6
OFF
Bypass DI-7
d3-01
d3-02
d3-03
d3-04
L5-01
L2-02
Z1-08
Z1-07
o1-03
UB-02 (Bit 2)
OFF
Bypass DI-3
UB-02 (Bit 3)
OFF
Bypass DI-4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents