YASKAWA Z1000 Technical Manual page 211

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Setting 33: DRIVE/BYPASS Select
When this is selected, the DRIVE/BYPASS select function command will come from a digital input while the DRV/BYP key
on the HOA operator will be ignored.
Input OFF: Drive Mode is selected.
Input ON: Bypass Mode is selected.
Setting 34: Fault Reset
Resets any faults that are present.
Setting 35: External Fault (EF0)
Issues external fault EF0 to the drive from the bypass. Use parameter Z1-30 to modify the fault delay time.
Setting 36: External Fault (EFB)
Triggers external EFB on the bypass.
Setting 37: Run Reverse (AUTO Mode)
Starts and stops the bypass in reverse when Z1-08 is set to 1.
Setting 38: Fire Stat
Stops the drive from running and displays "Fire Stat" on the keypad regardless of Z1-08 setting.
Note:
Available in bypass controller software versions VST800400 and later.
Setting 39: Freeze Stat
Stops the drive from running and displays "Freeze Stat" on the keypad regardless of Z1-08 setting.
Note:
Available in bypass controller software versions VST800400 and later.
Setting 40: Smoke Alarm
Stops the drive from running and displays "Smoke Alarm" on the keypad regardless of Z1-08 setting.
Note:
Available in bypass controller software versions VST800400 and later.
Setting 41: Over Pressure
Stops the drive from running and displays "Over Pressure" on the keypad regardless of Z1-08 setting.
Note:
Available in bypass controller software versions VST800400 and later.
Setting 42: Low Suction
Stops the drive from running and displays "Low Suction" on the keypad regardless of Z1-08 setting.
Note:
Available in bypass controller software versions VST800400 and later.
Setting 43: Vibration Switch
Stops the drive from running and displays "Vibration Switch" on the keypad regardless of Z1-08 setting.
Note:
Available in bypass controller software versions VST800400 and later.
n
Z2-09 to Z2-16: Digital Input 1 to 8 Invert Select
No.
Z2-09
Z2-10
Z2-11
Z2-12
Z2-13
Z2-14
Z2-15
Z2-16
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Name
Digital Input 1 Invert Select
Digital Input 2 Invert Select
Digital Input 3 Invert Select
Digital Input 4 Invert Select
Digital Input 5 Invert Select
Digital Input 6 Invert Select
Digital Input 7 Invert Select
Digital Input 8 Invert Select
5.15 Z: Bypass Parameters
Setting Range
0, 1
0, 1
0, 1
0, 1
0, 1
0, 1
0, 1
0, 1
5
Default
0
0
0
0
0
0
0
0
211