YASKAWA Z1000 Technical Manual page 102

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

4.3 The Drive and Programming Modes
No.
Name
Z3-03
Serial Communications
(8502)
Baud Rate Select
Z3-04
Serial Communications
(8503)
Parity Select
Z3-05
Serial Communications
(8504)
Fault Select
Z3-06
Serial Communications
(8505)
Fault Time Select
Z3-07
Serial Communications
(8506)
Receive to Transmit Wait
Time
Z3-08
BACnet Device Object
(8507)
Identifier 0
Z3-09
BACnet Device Object
(8508)
Identifier 1
<1> Available in Quick Setting Group in bypass controller software versions VST800299 and earlier.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Values shown are specific to 208 Vac. Double the value for 480 Vac.
<4> The number of decimal places in the parameter value depends on the drive model.
<5> Default value is 0 in bypass controller software versions VST800297 and earlier.
<6> Setting 2 is available in bypass controller software versions VST800298 and later.
<7> Selecting setting 0, 1, or 2 will trigger an oPE29 error when using BACNet communication in bypass controller software versions VST800400 and
later.
102
Selects the bypass serial communications speed.
<7>
0: 1200
<7>
1: 2400
<7>
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 76800
8: 115200
Selects the bypass serial communications parity.
0: No Parity
1: Even Parity
2: Odd Parity
Selects the action to take when a serial communications fault is detected.
0: Ignore. A serial communications loss will result in no action being taken.
1: Alarm only.
2: Fault witn EF0. An EF0 will be sent to the drive. If running in Bypass, the
bypass contactor will NOT open and the motor will keep running.
3: Fault with EF0 and Open Contactors. An EF0 fault will be sent to the drive
and the bypass contactor (K3) will be opened.
4: Alarm and run at preset speed set in Z3-10. Display AL14 alarm on Operator
Sets the time allowed to elapse since receiving serial communications before
triggering a communications fault.
A setting of 0.0 will never time out.
Sets the time to delay a serial communications response to a serial
communications command. This parameter will only appear when
Z3-01 = 0, 1, or 2.
BACnet only.
Sets the least significant word of 22-bit virtual address. This parameter will
appear only when Z3-01 = 3.
BACnet only.
Sets the most significant word of 22-bit virtual address. This parameter will
appear only when Z3-01 = 3.
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Description
Refer to Defaults by Drive Model on page 356
Values
Page
Default: 3
215
Range: 0 to 8
Default: 0
215
Range: 0 to 2
Default: 1
215
Range: 0 to 4
Default: 2.0 s
Min.: 0.0
428
Max.: 99.9
Default: 5 ms
Min.: 0
428
Max.: 99 ms
Default: 1
Min.: 0
216
Max.: FFFF
Default: 0
Min.: 0
216
Max.: 003F
for details.