YASKAWA Z1000 Technical Manual page 353

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Z3-04
Serial Communications
(8503)
Parity Select
Z3-05
Serial Communications
(8504)
Fault Select
Z3-06
Serial Communications
(8505)
Fault Time Select
Z3-07
Serial Communications
(8506)
Receive to Transmit Wait
Time
Z3-08
BACnet Device Object
(8507)
Identifier 0
Z3-09
BACnet Device Object
(8508)
Identifier 1
Z3-10
(8509)
Cable Loss Preset Frequency
Z3-11
Communication Fault
(850A)
Detection Selection
Z3-12
(850B)
Network Digital Input Select
<1>
Z3-13
BACNet Command Register
(850C)
Retention
<3> <4>
<1> Available in bypass controller software versions VST800298 and later.
<2> Selecting settings 0, 1, or 2 will trigger an oPE29 error when using BACNet communication in bypass controller software versions VST800400
and later.
<3> Available in bypass controller software versions VST800400 and later.
<4> Parameter is effective only when Z3-01 = 3 (Serial Communications Protocol Select = BACnet), Z1-07 = 2 (Speed Reference Select = Bypass
Serial), and/or Z1-08 =2 (Run Command Select = Bypass Serial).
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Description
Selects the bypass serial communications parity.
0: No Parity
1: Even Parity
2: Odd Parity
Selects the action to take when a serial communications fault is detected.
0: Ignore. A serial communications loss will result in no action being taken.
1: Alarm only.
2: Fault with EF0. An EF0 will be sent to the drive. If running in Bypass mode,
the bypass contactor will NOT open and the motor will keep running.
3: Fault with EF0 and Open Contactors. An EF0 fault will be sent to the drive
and the bypass contactor (K3) will be opened.
4: Alarm and run at preset speed set in Z3-10. Display AL14 alarm on
Operator.
Sets the time allowed to elapse since receiving serial communications before
triggering a communications fault.
A setting of 0.0 will never time out.
Sets the time to delay a serial communications response to a serial
communications command.
BACnet only.
Sets the least significant word of 22-bit virtual address.
BACnet only.
Sets the most significant word of 22-bit virtual address.
When a serial communications fault is detected and Z3-05=4, the resulting
value will become the frequency reference.
Communication Fault Detection Selection
0: Disabled. Serial communications fault detection is completely disabled.
1: Enabled. Behavior defined by Z3-05.
Enables and disables control of the digital inputs over a network. Wiring to
the physical digital input is not required.
0: Disable
1: Enable
Determines whether to restore the frequency reference, bypass command, or
both upon the reapplication of power after losing power.
WARNING! Sudden Movement Hazard. Setting this parameter to 2 or
3 will allow the bypass unit to start before receiving a valid network
message. Clear all personnel from the drive, motor, and machine area
before reapplying power. Failure to comply could result in injury to
personnel.
0: Disable
1: Reference Only
2: Run/Stop Only
3: Ref & Run/Stop
B.14 Z: Bypass Parameters
Values
Page
Default: 0
Range: 0 to 2
Default: 1
Range: 0 to 4
Default: 2.0 s
Min.: 0.0
Max.: 99.9
Default: 5 ms
Min.: 0
Max.: 99 ms
Default: 1
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: 003F
Default: 0
Min.: 0.0 Hz
Max.: 60.0 Hz
Default: 1
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 3
215
215
215
215
216
216
216
216
216
217
B
353