YASKAWA Z1000 Technical Manual page 182

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

5.10 n: Special Adjustments
n
n3-13: Overexcitation Deceleration Gain
Multiplies a gain to the V/f pattern output value during Overexcitation Deceleration to determine the level of overexcitation.
The drive returns to the normal V/f value after the motor has stopped or when it is accelerating to the frequency reference.
No.
Name
Setting Range
Default
n3-13
Overexcitation Deceleration Gain
1.00 to 1.40
1.10
The optimum setting for n3-13 depends on the motor flux saturation characteristics.
• Gradually increase the gain to 1.25 or 1.30 to improve the braking power of Overexcitation Deceleration.
• Lower n3-13 when flux saturation characteristics cause overcurrent. A high setting sometimes causes overcurrent (oC),
motor overload (oL1), or drive overload (oL2). Lowering n3-21 can also help remedy these problems.
182