H3: Multi-Function Analog Inputs

No.
(Addr.
Name
Hex)
Terminal A1 Signal Level
H3-01
Selection
(410)
Term A1 Level
Terminal A1 Function
H3-02
Selection
(434)
Term A1 FuncSel
H3-03
Terminal A1 Gain Setting
(411)
Terminal A1 Gain
H3-04
Terminal A1 Bias Setting
(412)
Terminal A1 Bias
Terminal A2 Signal Level
H3-09
Selection
(417)
Term A2 Level
Terminal A2 Function
H3-10
Selection
(418)
Term A2 FuncSel
H3-11
Terminal A2 Gain Setting
(419)
Terminal A2 Gain
H3-12
Terminal A2 Bias Setting
(41A)
Terminal A2 Bias
Analog Input Filter Time
H3-13
Constant
(41B)
A1/A2 Filter T
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
H2 Multi-Function Digital Output Settings
LCD Display
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
Watt-hour Pulse
the kWh count.
During SpdSrch
Closed: Speed Search is being executed.
Closed: A Fast Stop command has been entered from the operator or input
During Fast Stop
terminals.
Closed: oH pre-alarm time limit has passed.
Closed: Internal cooling fan alarm
Fan Alrm Det
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
0: 0 to 10 V with zero limit
1: 0 to 10 V without zero limit
2: 4-20 mA
3: 0-20 mA
Note:
Use jumper switch S1 to set input terminal A1 for current or
voltage.
Sets the function of terminal A1.
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
0: 0 to 10 V with zero limit
1: 0 to 10 V without zero limit
2: 4 to 20 mA
2: 4-20 mA
3: 0 to 20 mA
3: 0-20 mA
Note:
Use jumper switch S1 to set input terminal A2 for current or
voltage input signal.
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input
at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
Sets a primary delay filter time constant for terminals A1 and A2. Used for
noise filtering.
B.8 H Parameters: Multi-Function Terminals
Description
Description
0: 0-10V, (LowLim=0)
1: 0-10V, (BipolRef)
0: 0-10V, (LowLim=0)
1: 0-10V, (BipolRef)
Page
159
160
160
160
160
160
160
Values
Page
Default: 0
160
Range: 0 to 3
Default: 0
161
Range: 0 to 26
Default: 100.0%
Min.: -999.9
161
Max.: 999.9
Default: 0.0%
Min.: -999.9
161
Max.: 999.9
Default: 2
162
Range: 0 to 3
Default: 0
162
Range: 0 to 26
Default: 100.0%
Min.: -999.9
162
Max.: 999.9
Default: 0.0%
Min.: -999.9
162
Max.: 999.9
Default: 0.03 s
Min.: 0.00
162
Max.: 2.00
325