Advertisement

5.7 F: Options

5.7

F: Options

u

F6: Drive/Bypass Communications

n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No.
F6-01
Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)
Setting 1: Coast to Stop
Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)
Setting 3: Alarm Only (Continue Operation)
Setting 4: Alarm Only (Continue Operation Using the Frequency Reference Set in d1-04)
Setting 5: Alarm Only (Use the Deceleration Time Set to C1-02)
n
F6-02: External Fault from Bypass Controller Detection Selection
Determines the detection method of an external fault initiated by the bypass controller (EF0).
No.
F6-02
External Fault from Bypass Controller Detection Selection
Setting 0: Always detected
Setting 1: Detection during Run only
n
F6-03: External Fault from Bypass Controller Operation Selection
Determines drive operation when an external fault is initiated by the bypass controller (EF0).
No.
F6-03
External Fault from Bypass Controller Operation Selection
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
150
Parameter Name
Communications Error Operation Selection
Parameter Name
Parameter Name
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Setting Range
0 to 5
Setting Range
0, 1
Setting Range
0 to 3
Default
1
Default
0
Default
1