YASKAWA Z1000 Technical Manual page 147

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

Predefined V/f Patterns for Models Z1B1D030 to D211 and Z1B1B014 to B096
The values in the following graphs are specific to 208 Vac. Double the values for 480 Vac.
Setting = 0
50 Hz
200
14
7
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
200
35
6
0
1.3
25
50
Frequency (Hz)
Setting = 8
50 Hz
200
18
9
0
1.3 2.5
50
Frequency (Hz)
Setting = C
90 Hz
200
14
7
0
1.5 3
60
90
Frequency (Hz)
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Table 5.12 Rated Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
200
14
7
0
1.5 3
60
Frequency (Hz)
Table 5.13 Variable Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
200
50
7
0
1.3
25
50
Frequency (Hz)
Table 5.14 High Starting Torque, Settings 8 to B
Setting = 9
50 Hz
200
23
11
0
1.3 2.5
50
Frequency (Hz)
Table 5.15 Constant Output, Settings C to F
Setting = D
120 Hz
200
14
7
0
1.5 3
60
120
Frequency (Hz)
Setting = 2
60 Hz
200
14
7
0
1.5 3
50
60
Frequency (Hz)
Setting = 6
60 Hz
200
35
6
0
1.5
30
60
Frequency (Hz)
Setting = A
60 Hz
200
18
9
0
1.5 3
60
Frequency (Hz)
Setting = E
180 Hz
200
14
7
0
1.5 3
60
180
Frequency (Hz)
5.6 E: Motor Parameters
Setting = 3
72 Hz
200
14
7
0
1.5 3
60
72
Frequency (Hz)
Setting = 7
60 Hz
200
50
7
0
1.5
30
60
Frequency (Hz)
Setting = B
60 Hz
200
23
13
0
1.5 3
60
Frequency (Hz)
Setting = F
60 Hz
230
16.1
8.1
0
1.5 3
60
Frequency (Hz)
147