Z3: Bypass Control Communication - YASKAWA Z1000 Technical Manual

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

B.14 Z: Bypass Parameters
No.
(Addr.
Name
Hex)
Z2-16
(8572)
Digital Input 8 Invert Select
Z2-23
Digital Output 7 Function
(8579)
Select
Z2-24
Digital Output 8 Function
(857A)
Select
Z2-25
Digital Output 9 Function
(857B)
Select
Z2-26
Digital Output 10 Function
(857C)
Select
Z2-31
Safety Open Message
(8581)
Selection
<1>
<1> Available in bypass controller software versions VST800298 and VST800299.
<2> Available in bypass controller software versions VST800400 and later.
u

Z3: Bypass Control Communication

No.
(Addr.
Name
Hex)
Z3-01
Serial Communications
(8500)
Protocol Select
Z3-02
Serial Communications
(8501)
Node Address Select
Z3-03
Serial Communications
(8502)
Baud Rate Select
352
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Digital Output 1 Function Select
0: Serial Comm Controlled
1: K1 Drive Input Contactor
2: K2 Drive Output Contactor
3: K3 Bypass Contactor
4: K4 Motor 1 Select
5: K5 Motor 2 Select
6: READY (Drive and Bypass)
7: RUN Active (Drive or Bypass)
8: Drive RUN Active
9: Bypass RUN Active
10: HAND Mode Active
11: OFF Mode Active
12: AUTO Mode Active
13: Drive Mode Selected
14: Bypass Mode Selected
15: Drive or Bypass Fault Active
16: Drive Fault Active
17: Bypass Fault Active
18: Auto Transfer Active
19: Serial RUN Command Active
20: Damper Actuator Output
21: ON Always
22: Loss of Load Detected
<1>
23: Run Verify
<2>
24: Soft Start Run
99: Not Used
Sets the fault message displayed when an FB01 fault is triggered.
0: Safety Open
1: Fire Stat
2: Freeze Stat
3: Smoke Alarm
4: Over Pressure
5: Low Suction
6: Vibration Switch
Selects the bypass serial communications protocol.
0: Modbus
1: N2
2: P1
3: BACnet
Selects the bypass serial communications node address.
Selects the bypass serial communications speed.
<2>
0: 1200 bps
<2>
1: 2400 bps
<2>
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Description
Description
Values
Page
Default: 0
211
Range: 0, 1
Default: 7
212
Range: 0 to 24; 99
Default: 10
212
Range: 0 to 24; 99
Default: 12
212
Range: 0 to 24; 99
Default: 15
212
Range: 0 to 24; 99
Default: 0
212
Range: 0 to 6
Values
Page
Default: 3
213
Range: 0 to 3
Default: 1
Min.: 0
213
Max.: 127
Default: 3
215
Range: 0 to 8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents