N2 Specifications And Configuration; N2 Specifications And Configuration - YASKAWA Z1000 Technical Manual

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

F.1 N2 Specifications and Configuration
F.1

N2 Specifications and Configuration

The bypasses can be monitored and controlled by a controller on a Metasys N2 network (N2) using RS-485 technology. The
bypass act as slaves on the N2 network.
Up to 255 bypasses can communicate on a single N2 network. If more bypasses or N2 devices are required, another N2 network
is required.
The N2 node address is configurable by a parameter in the bypass. This defines the physical address of the bypass on the N2
network.
Once the addressing is set, a controller can initiate communication to the bypass. The bypass will perform the specified function
and then send a response back to the controller.
N2 specifications appear in the following table:
Item
Interface
Communication Parameters
Protocol
Max Number of Drives
424
Z1000
Bypass
Figure F.1 Connecting Multiple Bypasses to a Metasys N2 Network
RS-485
Communication Speed: 9600 bps
Data Length: 8-bit (fixed)
Parity: None
Stop Bit: 1-bit (fixed)
Metasys N2
255 per N2 Network Segment
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Metasys Field
Controller
N2
Z1000
Z1000
Bypass
Bypass
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents