7-2. Checking the billing function settings (check before billing function trial
run)
From [Option] > [Output - Check sheet for billing function trial run] on the Initial Setting Tool, output the "Items to
be checked after the trial run" check sheet (Excel sheet). Two sheets exist in the Excel sheet output, the "Billing-
related item sheet" and the "Unit-related item sheet".
If there are multiple AE-200 systems, output an "Items to be checked after the trial run" check sheet for each
system.
7-2-1. Billing-related item sheet
There will be 1 billing-related item sheet for each AE-200 system.
[1]
[3]
[1] Billing function settings
Check that none of the settings differ from those set in section 6-7-1 "Billing function settings".
① Apportioning with metering device (Use/Non-use)
② Power source of A-control unit (Same power source (O/U - I/U)/Separated power source (O/U - I/U))
③ Outdoor unit operating electric energy (Capacity save amount/Thermo-ON time/FAN operation time)
④ Outdoor unit standby electric energy (Apportion/Not apportion)
⑤ Indoor unit operating electric energy (Apportion/Not apportion)
⑥ Indoor unit standby electric energy (Apportion/Not apportion)
WT07442X02
[2]
[4]